Plan Review Notes
Plan Review Notes For Project Z14080024
Project Number Z14080024
Review Stop STORM
Sequence Number 1
Notes
Date Text
2014-09-10 10:53:55NO OBJECTION TO THE REZONING REQUEST. THE FOLLOWING
 COMMENTS SHOULD BE ADDRESSED PRIOR TO FUTURE SUBMITALS
 TO THE PLANNING DEPT. OR THE ENGINEERING DEPT.
 1. ON SHEET 1 OF 3, CONCEPTUAL ENGINEERING PLAN:
 A. MOVE "(R/W TO BE ABANDONED)" NOTE ON 14TH STREET TO
 WEST OF THE GATES.
 B. ADD NOTE THAT WEST END OF ALLEY R/W WILL BE
 ABANDONED.
  
 2. IF ALLLEY R/W IS NOT ABANDONED, AN EASEMENT WILL BE
 NEEDED FOR THE DRAINAGE PIPE CROSSING THE ALLEY R/W.
  
 3.THE EXFILTRATION CALCULATIONS FOR THE SOUTH PORTION
 ON SHEET 3 OF 3, INDICATE 170 LF OF TRENCH WILL BE
 PROVIDED. SHEET 1 OF 3 ONLY SHOWS 150 LF OF TRENCH.
  
 4. THE AREAS USED IN THE EXFILTRATION TRENCH
 CALCULATIONS ON SHEET 3 OF 3 DO NOT MATCH THE AREAS
 SHOWN ON THE SITE AREA MAP AT THE TOP OF SHEET SP-1.
  
 5. PLACE THE WEIR WITH CONTROL ELEVATION 16.00 ON THE
 NORTH SIDE OF THE EXISTING CB.
  
 6. CONSIDER INSTALLING THE WEIRS IN THE EXISTING MH IN
 14TH STREET (AREA TO BE ABANDONED).
  
 7. DRAINAGE STRUCTURE WILL BE NEEDED AT EAST LIMIT OF
 14TH ST R/W ABANDONMENT. DRAINAGE SYSTEM UPSTREAM OF
 DRAINAGE STRUCTURE WOULD THEN NO LONGER BE MAINTAINED
 BY THE CITY.
  
 8. INDICATE VERTICAL DATUM ON CONCEPTUAL ENGINEERING
 PLAN (SHOULD BE NGVD 1929).
  
 9. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 10. IDENTIFY THE CONFLICTS BETWEEN DRAINAGE AND
 WATER/SEWER MAINS ON THE CONCEPTUAL ENGINEERING PLAN.
  
 11. CITY NOW REQUIRES THE MILLING AND RESURFACING A
 MINIMUM OF 1" OF ASPHALT FOR 50 FEET EACH SIDE OF A
 TRENCH CUT AND FOR FULL LANE WIDTH.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 (561) 494-1120
  
  