| 2014-09-08 13:44:09 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | UPDATE 9/9/14. SCOTT LEWIS,OWNER OF PROPERTY, CONTACTED |
| | ME VIA TELEPHONE AND DISCUSSED THE NOTED CONCERNS |
| | BELOW. THIS PROPERTY IS CURRENT AND COMPLIANT WITH ITS |
| | FIRE INSPECTIONS AND THE CONCERNS RELATED TO THE |
| | PROPOSED EXPANSION WILL BE ADDRESSED ACCORDINGLY. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE |
| | DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF |
| | POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. CONSTRUCTION SHALL COMPLY WITH NFPA 101, FLORIDA |
| | FIRE PREVENTION CODE, 2010 EDITION INCLUDING CHAPTER |
| | 42, STORAGE OCCUPANCIES AND NFPA 1, INCLUDING |
| | 13.3.3.25, NEW STORAGE OCCUPANCIES AND CHAPTER 34, |
| | GENRAL STORAGE. |
| | |
| | 6. BASED ON THE PROPOSED SUBMITTAL A NFPA 13 COMPLAINT |
| | FIRE SPRINKLER SYSTEM IS REQUIRED FOR THE BUILDING IN |
| | THIS PROJECT. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO |
| | BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE |
| | PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 7. A MONITORED FIRE ALARM SYSTEM IS ALSO REQUIRED FOR |
| | THE BUILDINGS OF THIS PROJECT. SEPARATE SHOP DRAWINGS, |
| | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY |
| | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 8. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL BE |
| | PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, EXITS, EMERGENCY LIGHTING, DEAD-END |
| | CORRIDORS AND ALL FIRE SAFETY EQUIPMENT. |
| | |
| | 9. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED |
| | AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED |
| | THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE. |
| | |
| | 10. ALL COMMODITIES FOR EACH BUILDING OR OUTSIDE SPACE |
| | SHALL BE IDENTIFIED, INCLUDING TYPE OF RACKS, HEIGHTS, |
| | PALLET TYPE, PACKAGING, ETC. |
| | |
| | 11. THE CONSTRUCTION TYPE OF THE BUILDING SHALL BE |
| | CLEARLY IDENTIFIED. |
| | |
| | 12. OUTSIDE AREAS # 1 & # 2 MAY REQUIRE SPRINKLER |
| | SYSTEM. NOTE # 10 AND 11 ABOVE. |
| | |
| | 13. FIRE FLOW CALCULATIONS SHALL BE SUBMITTED WITH |
| | IDENTIFED FIRE HYDRANTS THAT MEET THE REQUIRED FLOW. |
| | |
| | 14. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF |
| | FIRE PREVENTION. |
| | |
| | 15. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS |
| | (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND |
| | COORDINATED WITH THE BUREAU OF FIRE PREVENTION. |
| | |
| | 16. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS |
| | BUILDING AND GATE AREAS. |
| | |
| | 17. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR |
| | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR |
| | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE |
| | PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY |
| | DOOR. |
| | |
| | |
| | |
| |