Notes
Date Text
2014-09-08 13:44:09THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 UPDATE 9/9/14. SCOTT LEWIS,OWNER OF PROPERTY, CONTACTED
 ME VIA TELEPHONE AND DISCUSSED THE NOTED CONCERNS
 BELOW. THIS PROPERTY IS CURRENT AND COMPLIANT WITH ITS
 FIRE INSPECTIONS AND THE CONCERNS RELATED TO THE
 PROPOSED EXPANSION WILL BE ADDRESSED ACCORDINGLY.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. CONSTRUCTION SHALL COMPLY WITH NFPA 101, FLORIDA
 FIRE PREVENTION CODE, 2010 EDITION INCLUDING CHAPTER
 42, STORAGE OCCUPANCIES AND NFPA 1, INCLUDING
 13.3.3.25, NEW STORAGE OCCUPANCIES AND CHAPTER 34,
 GENRAL STORAGE.
  
 6. BASED ON THE PROPOSED SUBMITTAL A NFPA 13 COMPLAINT
 FIRE SPRINKLER SYSTEM IS REQUIRED FOR THE BUILDING IN
 THIS PROJECT. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO
 BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE
 PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 7. A MONITORED FIRE ALARM SYSTEM IS ALSO REQUIRED FOR
 THE BUILDINGS OF THIS PROJECT. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 8. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL BE
 PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXITS, EMERGENCY LIGHTING, DEAD-END
 CORRIDORS AND ALL FIRE SAFETY EQUIPMENT.
  
 9. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED
 AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED
 THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE.
  
 10. ALL COMMODITIES FOR EACH BUILDING OR OUTSIDE SPACE
 SHALL BE IDENTIFIED, INCLUDING TYPE OF RACKS, HEIGHTS,
 PALLET TYPE, PACKAGING, ETC.
  
 11. THE CONSTRUCTION TYPE OF THE BUILDING SHALL BE
 CLEARLY IDENTIFIED.
  
 12. OUTSIDE AREAS # 1 & # 2 MAY REQUIRE SPRINKLER
 SYSTEM. NOTE # 10 AND 11 ABOVE.
  
 13. FIRE FLOW CALCULATIONS SHALL BE SUBMITTED WITH
 IDENTIFED FIRE HYDRANTS THAT MEET THE REQUIRED FLOW.
  
 14. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 15. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 16. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING AND GATE AREAS.
  
 17. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
  
  