2014-12-19 17:05:441. NOTE 4 ON SHEET C5.01 LISTS NAVD88.
  
 2. DRIVEWAY ON FLAGLER DRIVE AT SW CORNER OF SITE IS
 SHOWN TO GET NEW VALLEY GUTTER INSTEAD OF REPLACEMENT
 OF CURB WITH TYPE 'F' CURB AND GUTTER AND THE REMOVAL
 OF THE DRIVEWAY APRON BETWEEN THE CURB AND SIDEWALK.
 THIS WORK SHOULD ALSO BE SHOWN ON THE DEMOLOTION PLAN
 FOR CONTINUITY.
  
 3. PRIOPOSED STORM MISSING FROM THE LIGHTING AND
 PHOTOMETRICS PLANS.
  
 4. THERE IS NOT ANY "CONTROLS" IN STRUCTURE S-10 TO
 REGULATE STORMWATER RUNOFF INTO THE EXFILTRATION
 TRENCH. IT APPEARS EXFILTRATION TRENCH WILL BE
 SURCHARGED ONLY WHEN THE RETENTION AREA FILLS UP.
  
 5. SWPPP SHOULD INCLUDE PROTECTION OF INLETS ON FLAGLER
 DRIVE.
  