Plan Review Notes
Plan Review Notes For Project Z14080019
Project Number Z14080019
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-09-08 14:55:56THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE BUILDING CONSTRUCTON SHALL COMPLY WITH NFPA 101,
 LIFE SAFETY CODE, FLORIDA 2010 EDITION, INCLUDING
 CHAPTER 12, NEW ASSEMBLY OCCUPANCIES.
  
 6. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS
 REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 7. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 8. PLEASE PROVIDE FIRE FLOW CALCULATIONS AND ENSURE THE
 PROPOSED FIRE HYDRANT IS SUFFICIENT TO PROVIDE THE
 FLOW.
  
 9. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL BE
 PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXITS, EXIT DISCAHRGES, PUBLIC WAYS,
 EMERGENCY LIGHTING, DEAD-END CORRIDORS AND ALL FIRE
 SAFETY EQUIPMENT.
  
 10. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED
 AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED
 THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE.
  
 11. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE
 CLEARLY IDENTIFIED AND INDICATED ON THE PLAN.
  
 12. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 13. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY
 WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 14. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 15. THE ENTRY ACCESS ROAD SHOWS 16 FEETT AND THE ACCESS
 DRIVE IS 12 FEET WIDE. THESE ACCESS ROAD ARE FIRE LANES
 AND ARE REQUIRED TO BE 20 FEET WIDE.
  
 16. THE DOUBLE ENTRY GATES ARE REQUIRED TO HAVE KNOX
 KEY SWITCHES FOR 24 HOUR EMERGENCY ENTRY ACCESS.
  
  
  
  
  
  
  