| Plan Review Notes For Project Z14080019 |
| Project Number |
Z14080019 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-10 12:10:29 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR PERMITTING. | | | | | | 2. THE PROPOSED BUILDING WILL BE IN FLOOD ZONE AE. THE | | | ELEVATION OF THE FIRST FLOOR OF THE BUILDING AND ALL | | | ASSOCIATED MECHANICAL EQUIPMENT (CHILLERS, GENERATORS | | | ETC.) SHALL BE 6 INCHES (FREEBOARD) ABOVE THE BASE | | | FLOOD ELEVATION. | | | | | | 3. ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER | | | THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY | | | WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE. | | | | | | 4. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL | | | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS | | | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND | | | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA | | | BUILDING CODE | | | | | | 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH | | | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND | | | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF | | | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. | | | | | | 6. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE | | | OBTAINED BEFORE COMMENCING THE WORK.94, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
| |