| Plan Review Notes For Project Z14070022 |
| Project Number |
Z14070022 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-11-17 15:16:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THIS WAS THE FIRST I HAVE HAD THE OPPORTUNITY TO REVIEW | | | THE FLOOR PLAN. | | | | | | THE MEZZANINE REQUIRES A SECOND MEAS OF EGRESS AND | | | SHALL NOT BE APPROVED IF IT IS TO BE SUBMITTED WITH | | | ONLY ONE. | | | | | | PLEASE REVIEW AND PROVIDE YOUR JUTIFICATION FOR ONLY | | | PROVIDING FOR THE ONE AND/OR REDESIGN WITH A SECOND | | | EXIT REMOTE FROM THE OTHER. | | | | | | ALL OTHER COMMENTS HAVE BEEN ADDRESSED. | | | | | | THIS CONCERN CAN BE ADDRESSED DURING FORMAL BUILDING | | | PLAN REVIEW. |
| |