Plan Review Notes
Plan Review Notes For Project Z14060003
Project Number Z14060003
Review Stop PU
Sequence Number 2
Notes
Date Text
2014-09-16 16:47:019-16-2014
  
 WATER
 THE RESUBMITTED PLANS PROVIDED THE NECESSARY PROPOSED
 UTILITIES AND LOCATIONS.
 THE PROPOSED 6? FIRE LINE WILL REQUIRE A CUT-IN TEE TO
 THE EXISTING 6? DI WATER MAIN (THIS IS CORRECTLY CALLED
 OUT IN THE PLANS).
 OUR PUBLIC UTILITIES DEPARTMENT HAS ALREADY LOCATED THE
 NECESSARY SYSTEM VALVES THAT WILL ALLOW THE 6? LINE TO
 BE SHUT-DOWN FOR THE CUT-IN TEE AND 6? FIRE LINE
 CONSTRUCTION. THESE VALVES ARE IN OPERABLE CONDITION
 AND SHOULD SUCCESSFULLY ISOLATE THIS LINE FROM THE
 MAIN.
  
 SANITARY SEWER
 THE EXISTING LATERAL WILL BE USED TO CONVEY SANITARY
 FLOWS TO THE CITY?S COLLECTION SYSTEM WITHOUT
 MODIFICATION.
  
  
 JACKSON LOEBIG
 O&M SUPERINTENDENT
 PUBLIC UTILITIES DEPARTMENT
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
  
 TEL: 561 494-1067
 CELL: 561 951-7656
  
2014-09-12 14:33:40PURSUANT TO EMAIL RECEIVED FROM JACKSON LOEBIG ON
 SEPTEMBER 10, 2014, REVISED PLANS SUFFICIENTLY
 ADDRESSED ALL PREVIOUS COMMENTS.