Plan Review Notes
Plan Review Notes For Project Z14040015
Project Number Z14040015
Review Stop STORM
Sequence Number 1
Notes
Date Text
2014-05-08 16:07:471. INDICATE VERTICAL DATUM ON THE ENGINEERING PLANS.
 2. LANDSCAPE PLANS SHOW WHAT APPEAR TO BE A/C PADS
 BEHIND THE UNITS. WILL THESE PADS INTERFERE WITH THE
 PROPOSED SWALE?
 3. SHOW SPOT GRADES ALONG THE INVERT OF THE SWALE.
 4. LANDSCAPE PLANS SHOW TREES TO BE PLANTED NEAR SEWER
 LATERALS.
 5. VERIFY SUFFICIENT COVER WILL BE PROVIDED OVER THE
 PROPOSED STORM PIPE FOR THE PIPE MATERIAL SELECTED.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT