Plan Review Notes
Plan Review Notes For Project Z14040015
Project Number Z14040015
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-04-30 16:59:22THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. ALL CONSTRUCTION SHALL COMPLY WITH CHAPTER 42, ONE
 AND TWO FAMILY DWELLINGS, NFPA 101, LIFE SAFETY CODE,
 FLORIDA 2010 EDITION.
  
 6. A FIRE LOAD CALCULATION FOR THE SITE IS REQUIRED TO
 DETERMINE ON SITE FIRE HYDRANTS.
  
 7. THE COMMON AREAS, POOL, LAUNDRY AND REC CENTER SHALL
 BE REQUIRED TO HAVE AN ANNUAL FIRE INSPECTION.
  
  
  