| 2014-05-14 11:23:01 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. SHEET C2.1 THROUGH C4.1 SHOW THE STEPS LEADING UP TO |
| | THE RECREATION CENTER ENTRANCE DOOR. ALL |
| | NON-RESIDENTAIL BUILDINGS MUST BE ACCESSIBLE AND THERE |
| | SHOULD ATT LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH |
| | SECTIONS 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, |
| | CONNECTING ACCESSIBLE BUILDINGS OR FACILITY ENTRANCES |
| | WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE |
| | BUILDING OR FACILITY |
| | |
| | 3. ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER |
| | THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY |
| | WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 4. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE |
| | |
| | 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. THE |
| | EQUIVALENT REQUIREMENTS FOR ONE AND TWO FAMILY |
| | DWELLINGS, AND TOWNHOUSES ARE IN SECTION R302 OF |
| | FLORIDA BUILDING CODE (RESIDENTIAL). |
| | |
| | 6. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE |
| | OBTAINED BEFORE COMMENCING THE WORK. |
| | |
| | 7. FOR STREET ADDRESSING CONTACT SCOTT ALEF, GIS |
| | SUPPORT SPECIALIST, AT (561) 494 1094, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |