Plan Review Notes
Plan Review Notes For Project Z14030060
Project Number Z14030060
Review Stop STORM
Sequence Number 2
Notes
Date Text
2014-08-20 14:32:49SEE ENGINEERING COMMENTS
2014-06-02 19:32:591. DRAINAGE STRUCTURE S-202 APPEARS TO BE NEW. PROPOSED
 PIPE BETWEEN S-202 AND CS-2 WILL BE IN CONFLICT WITH
 EXISTING 6" WATER MAIN TO BE ABANDONED. CAN CS-2
 CONNECT TO EXISTING CURB INLET TO THE SOUTH OF CS-2
 INSTEAD? IT APPEARS IT WOULD CLEAR THE SANITARY MAIN IN
 THE ALLEY.
 2. SURVEY SHOWS THE GRATE ELEVATION OF THE EXISTING
 CURB INLET IN THE ALLEY TO BE 23.13 FT NGVD. THE PAVING
 AND DRAINAGE PLAN CALLS OUT A GRATE ELEVATION OF 22.0
 FT NGVD. LIKEWISE, THE GRATE ELEVATIONS FOR PROPOSED
 DRAINAGE STRUCTURES S-201, CS-2, CS-1 AND S-301 ON THE
 PAVING AND DRAINAGE PLAN ARE SHOWN TO BE MORE THAN 1
 FOOT BELOW EXISTING GRADES OF THE ALLEY AND ROSEMARY
 AVENUE.
 3. VERIFY THE WIDTH OF THE CONTROL STRUCTURES CAN "FIT"
 BOTH A WEIR BOX AND BAFFLE AND HAVE SUFFICIENT SPACE TO
 INSTALL BOTH.
 4. ON THE BAFFLE DETAIL, INDICATE MINIMUM DISTANCE
 BETWEEN BOTTOM OF BAFFLE AND INVERT OF EXFILTRATION
 TRENCH PIPE.
 5. DRAINAGE CALCULATIONS ON SHEET C3 INDICATE THE
 3-YEAR 1-HOUR DESIGN STORM TO BE 1 INCH. PER FDOT IDF
 CURVES, 3-YEAR 1 HOUR STORM IS CLOSER TO 2.8 INCHES.
 6. VALIDATE THE USE OF THE SFWMD EXFILTRATION TRENCH
 STANDARD FORMULA WITHOUT MODIFICATION WITH ONE SIDE OF
 THE TRENCH NEARLY ADJACENT TO THE WALL OF THE
 UNDERGROUND PARKING STRUCTURE.
 7. INDICATE HOW THE DRAINAGE OF THE UNDERGOUND PARKING
 STRUCTURES WILL BE MANAGED.
 8. TIE ROOF DRAINS INTO THE ONSITE DRAINAGE SYSTEM OR
 DISCAHRGE TO PERVIOUS AREAS WHERE POSSIBLE.
 9. WITH THE ENGINEERING PERMIT APPLICATION SUBMIT A
 STORMWATER POLLUTION PROTECTION PLAN.
 10. PRIOR TO CONSTRUCTION OR DEMOLITION, SUBMIT A COPY
 OF THE FDEP GENERAL PERMIT FOR STORMWATER DISCHARGES
 ASSOCIATION WITH CONSTRUCTION SITES (NPDES PERMIT).
 11. WATER MAIN VALVES AND SANITARY LATERALS SHOULD NOT
 BE LOCATED NEAR OR UNDER TREE PLANTERS.
 12. ON THE ARCHITECTURAL VIEWS, SETBACK LINES AND
 PROPERTY LINES ARE MISLABELED.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120
  
  
  