| 2014-04-09 11:21:47 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. NO ACCESSIBLE PARKING SPACES ARE CURRENTLY SHOWN. |
| | PER THE FAIR HOUSING ACT, AT LEAST 2% OF THE PARKING |
| | SPACES PROVIDED FOR THE DWELLING UNITS MUST BE |
| | ACCESSIBLE. ALSO, ACCESSIBLE PARKING SPACES SERVING THE |
| | NON-RESIDENTIAL AREAS OF THE BUILDINGS SHALL BE |
| | PROVIDED IN NUMBERS SUFFICIENT TO COMPLY WITH SECTION |
| | 208.2 OF FLORIDA ACCESSIBILITY CODE, |
| | |
| | 3. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE |
| | ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE |
| | SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING |
| | TO AN ACCESSIBLE ENTRANCE FOR EACH |
| | BUILDING. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL |
| | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE |
| | |
| | 4. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, |
| | ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A |
| | PARKING STRUCTURE, SHALL BE VAN ACCESSIBLE AND DESIGNED |
| | IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 5. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE |
| | |
| | 6. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 7. ENCLOSED PARKING GARAGES MUST HAVE EXHAUST SYSTEMS |
| | DESIGNED TO MINIMIZE NOISE LEVELS USING INLINE FAN |
| | SILENCERS OR OTHER APPROVED METHODS. |
| | |
| | 8. THE NEW BUILDINGS SHALL BE SEPARATED FROM THE |
| | EXISTING BUILDINGS BY FIRE WALLS DESIGNED IN ACCORDANCE |
| | WITH SECTION 706 OF FLORIDA BUILDING CODE, OR THEY MUST |
| | BE CONSIDERED AS ADDITIONS AS COVERED BY CHAPTER 10 OF |
| | THE FLORIDA EXISTING BUILDING CODE. |
| | |
| | 9. THE BRIDGES BETWEEN THE BUILDINGS AT LEVEL 5 AND |
| | LEVEL 6 SHALL BE DESIGNED IN ACCORDANCE WITH SECTION |
| | 3104 OF FLORIDA BUILDING CODE SUCH THAT THE BUILDINGS |
| | ARE CONSIDERED SEPARATE. |
| | |
| | 10. SHEET A-4 SHOWS A LONG DEAD END CORRIDOR FROM THE |
| | RESIDENTIAL UNITS TO THE CLOSEST EXIT STAIR. PER |
| | SECTION 1018.4 OF FLORIDA BUILDING CODE, THE DEAD END |
| | CORRIDOR SHALL NOT EXCEED 50 FEET. |
| | |
| | 11. IT IS NOTED THAT ELEVATOR LOBBIES ARE NOT SHOWN. |
| | THE BUILDING AND BUILDING SYSTEMS MUST MEET ONE OF THE |
| | EXCEPTIONS GIVEN IN SECTION 1018.4.1 OF FLORIDA |
| | BUILDING CODE (SUCH AS ELEVATOR HOISTWAY |
| | PRESSURIZATION), IF ELEVATOR LOBBIES ARE NOT PROPOSED. |
| | |
| | 12. IT IS NOTED THAT WIDENING OF THE ALLEY IS PROPOSED |
| | TO ACCOMODATE TWO-WAY VEHICULAR TRAFFIC. ON SHEET A-2, |
| | NO EXIT DISCHARGE DOOR IS YET SHOWN FOR THE STAIRWAY |
| | ADJACENT TO THE ALLEY, AND WHEN IT IS SHOWN THE EXIT |
| | DISCHARGE DOOR SHALL BE RECESSED SUCH THAT IT DOES NOT |
| | SWING INTO THE VEHICULAR TRAVEL LANE. |
| | |
| | 13. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE |
| | OBTAINED BEFORE COMMENCING THE WORK. |
| | |
| | 14. FOR STREET ADDRESSING CONTACT SCOTT ALEF, GIS |
| | SUPPORT SPECIALIST, AT (561) 494 1094, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |