Plan Review Notes
Plan Review Notes For Project Z14030056
Project Number Z14030056
Review Stop STORM
Sequence Number 1
Notes
Date Text
2014-04-04 11:47:331. CROSS SLOPE OF WALKWAY SHOULD DRAIN TO INTERIOR OF
 SITE AND NOT TOWARD THE INTRACOASTAL WATERWAY.
 2. WILL THE PROPOSED CONTROL STRUCTURE BE LOCATED
 WITHIN THE WALKWAY?
 3. SHOW UTILITIES ON THE LANDSCAPE PLANS.
 4. PROVIDE WATER QUALITY TREATMENT FOR STORMWATER
 RUNOFF PER SFWMD VOLUME CRITERIA.
 5. INCLUDE WITH THE ENGINEERING PERMIT APPLICATION THE
 FOLLOWING:
 - SIGNED AND SEALED DRAINAGE CALCULATIONS AND LAND USE
 BREAKDOWN (PERVIOUS/IMPERVIOUS/BUILDING/ETC.)
 - SIGNED AND SEALED ENGINEERING PLANS INCLUDING PAVING,
 GRADING AND DRAINAGE PLAN AND AN EROSION CONTROL PLAN
 6. PROVIDE BEFORE START OF CONSTRUCTION THE FOLLOWING
 PERMITS:
 - SFWMD ERP
 - FDEP NPDES
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120
  