Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-03-31 11:08:24THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 1. ON PAGE C200, THE FDC'S AND FIRE HYDRANTS MAY NOT BE
 LOCATED IN THE MOST EFFICIENT OR EFFECTIVE STRATEGIC
 LOCATIONS FOR ENGINE/PUMPER ACCESS AND OPERATIONS. THE
 BUREAU WOULD LIKE TO FURTHER REVIEW ALTERNATIVE
 LOCATIONS WITH FIRE OPERATIONS TO ENSURE OPERATIONAL
 EFFICIENCIES. ONE LOCATION TO CONSIDER IS TO LOCATE ONE
 CENTRALLY ON THE ENTRANCE ROAD BY THE DROP OFF AREA.
 THE OTHER WOULD BE ON THE NORTH END CLOSER TO THE ROAD
 AND ENTRANCE WAY.
  
 2. ON PAGE C100, THE PROPOSED MOUNTABLE CURB FOR FIRE
 DEPARTMENT ACCESS DOES NOT PROVIDE ANY DETAILS TO BE
 ABLE TO DETERMINE ACCEPTANCE. FURTHER DETAIL IS NEEDED.
  
 3. ON PAGE C100, THE PROPOSED 20' STABILIZED FIRE TRUCK
 ACCESS ROUTE DOES NOT PROVIDE ANY DETAILS TO DETERMINE
 ACCEPTANCE. FURTHER DETAIL IS NEEDED.
  
 THIS REVIEW WAS APPROVED PENDING THE ADDRESSING OF THE
 ABOVE COMMENTS.
  