Plan Review Notes
Plan Review Notes For Project Z14030044
Project Number Z14030044
Review Stop STORM
Sequence Number 2
Notes
Date Text
2014-06-02 20:20:10SITE PLAN APPROVED WITH THE FOLLOWING CONDITIONS:
 1. ON FLOOR PLAN SHEET A101, INDICATE CATCH BASIN DRAIN
 FROM COMPACTOR PAD WILL TIE INTO GREASE TRAP/SANITARY
 SYSTEM RATHER THAN TIE INTO STORM LINE.
 2. ON SHEET C-02, CHANGE REFERENCES TO WEST PALM BEACH
 PUBLIC HEATLH UNIT TO PALM BEACH COUNTY HEALTH
 DEPARTMENT.
 3. CORRECT DIMENSIONS/ELEVATIONS SHOWN ON THE
 EXFILTRATION TRENCH DETAIL ON SHEET C-07 TO MATCH THE
 PAVING, GRADING AND DRAINAGE PLAN SHEET C-06.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120
  