Plan Review Notes
Plan Review Notes For Project Z14030044
Project Number Z14030044
Review Stop PU
Sequence Number 1
Notes
Date Text
2014-04-02 16:32:12APRIL 4, 2014
  
 SANITARY SEWER
  
 ON APRIL 1, 2014, CITY SANITARY COLLECTIONS CREWS
 JETTED AND TV'D THE LATERAL (49.7 FEET) FROM THE SITE
 CLEAN-OUT NEAREST BELVEDERE TO THE DOWNSTREAM MANHOLE
 (SSM02816). THE LINE IS CLEAR AND FREE FROM DEFECTS.
  
 QUESTION: REGARDING THE SANITARY LINE FROM THE TRASH
 COMPACTOR DRAIN: IS THIS A TYPICAL CARDBOARD COMPACTOR?
 OR WILL THIS BE COMPACTING OTHER FOOD AND/OR ORGANIC
 WASTES? IF THE LATTER IS CHOSEN, THE UTILITY WOULD LIKE
 THE OPPORTUNITY TO DISCUSS AN ADDITIONAL GREASE TRAP
 FOR THE PURPOSE OF INTERCEPTING THESE WASTES PRIOR TO
 ENTERING THE COLLECTION SYSTEM.
  
  
 POTABLE WATER
  
 ON APRIL 3, 2014, STAFF FROM THE CITY?S METER SHOP
 ALONG WITH THEIR CERTIFIED BACKFLOW TECHNICIAN VISUALLY
 INSPECTED THE LOCATIONS FOR THE POTABLE WATER AND FIRE
 LINE BACKFLOWS AND APPURTENANCES. THE BACKFLOWS FOR THE
 POTABLE METER CONNECTIONS DID NOT LOOK TO BE IN GOOD
 CONDITION. PLEASE BE ADVISED THAT THESE MAY NOT PASS
 INSPECTION BY A CERTIFIED BACKFLOW TECHNICIAN.
  
  
  
 FIRE LINE DDC
  
 THE CURRENT DDC ALSO APPEARS TO BE WELL-WORN AND MAY
 NOT BE SERVICEABLE IN ITS' CURRENT CONDITION. PLEASE BE
 ADVISED THAT IT MAY NOT PASS INSPECTION BY A CERTIFIED
 BACKFLOW TECHNICIAN.
  
  
  
  