Plan Review Notes
Plan Review Notes For Project Z14020011
Project Number Z14020011
Review Stop STORM
Sequence Number 1
Notes
Date Text
2014-03-01 16:17:421. PROVIDE COPY OF SFWMD ERP PRIOR TO START OF
 CONSTRUCTION.
 2. PROVIDE COPY OF NPDES CGP PERMIT PRIOR TO START OF
 CONSTRUCTION.
 3. PROVIDE DRAINAGE CALCULATIONS, INCLUDING LAND USE
 BREAKDOWN (PERVIOUS, IMPERVIOUS, BUILDING, ETC), WATER
 QUALITY TREATMENT, ETC., WITH THE CITY'S ENGINEERING
 PERMIT APPLICATION.
 4. PROVIDE SWPPP PLAN WITH THE CITY'S ENGINEERING
 PERMIT APPLICATION.
 5. NO ENGINEERING PLANS OR CALCULATIONS PROVIDED.
 6. IDENTIFY WHICH DRAINAGE STRUCTURES WILL HAVE WEIR(S)
 AND/OR BAFFLES.
 7. SURVEY VERTICAL DATUM LISTED AS NAVD 1988. VERTICAL
 DATUM NEEDS TO BE NGVD 1929 PER CITY CODE.
 8. GENERAL NOTE 1 ON UTILITY PLAN C-1 INDICATES
 ELEVATIONS ARE REFERENCED TO NGVD 1929. ELEVATION DATA
 PROVIDED FOR EXISTING CATCH BASIN ON SHEET C-2 MATCHES
 DATA PROVIDED ON SURVEY (NAVD 1988 DATUM).
 9. PROVIDE WEIR ELEVATION FOR EXISTING DRAINAGE CONTROL
 STRUCTURE.
 10. SHOW EXISTING AND PROPOSED UTILITIES ON THE
 LANDSCAPE PLANS.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120