Plan Review Notes
Plan Review Notes For Project Z14010020
Project Number Z14010020
Review Stop B
Sequence Number 2
Notes
Date Text
2014-02-12 11:08:40DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE PLAN AMENDMENT. IT IS NOT A REVIEW FOR FULL
 COMPLIANCE WITH FLORIDA BUILDING CODE. THE FOLLOWING
 COMMENTS ARE TO BE ADDRESSED FOR PERMITTING.
  
 2. SHEET A1.0 SITE PLAN. THE SWING OF THE PARKING LOBBY
 ENTRANCE DOORS IS TOO CLOSE TO THE STEPS WHICH IMPEDES
 ACCESS TO AND FROM THE ACCESSIBLE PARKING SPACES. PER
 SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE ACCESSIBLE
 PARKING SPACES ARE TO BE LOCATED ON THE SHORTEST
 POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN
 ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN OF
 ACCESSIBLE PARKING
 SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA
 ACCESSIBILITY CODE
  
 3. SHEET A1.0 SITE PLAN. NEITHER OF THE ACCESSIBLE
 PARKING SPACES IS CALLED OUT AS VAN ACCESSIBLE. PER
 SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN
 EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING
 STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN
 ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY
 CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT
 SPACE AND VEHICULAR ACCESS ROUTE)
  
 4. SHEET A1.0 SITE PLAN. THE EXIT DISCHARGE DOOR FROM
 THE WEST STAIR DISCHARGES INSIDE THE BUILDING. PER
 SECTION 1027.1 OF FLORIDA BUILDING CODE, THE EXIT
 DISCHARGE DOOR SHALL DISCHARGE DIRECTLY TO THE OUTSIDE
 SO THAT USERS DO NOT RE-ENTER A FIRE RISK AREA WHEN
 LEAVING THE STAIR ENCLOSURE.
  
 5. SHEET A2.5 LEVEL 6 ROOF PLAN. ONLY ONE EXIT STAIR IS
 SHOWN SERVING THE ROOF GARDEN/DECK. PER SECTION 1021.1
 OF FLORIDA BUILDING CODE, TWO EXITS ARE REQUIRED.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  