| 2014-02-12 11:08:40 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE PLAN AMENDMENT. IT IS NOT A REVIEW FOR FULL |
| | COMPLIANCE WITH FLORIDA BUILDING CODE. THE FOLLOWING |
| | COMMENTS ARE TO BE ADDRESSED FOR PERMITTING. |
| | |
| | 2. SHEET A1.0 SITE PLAN. THE SWING OF THE PARKING LOBBY |
| | ENTRANCE DOORS IS TOO CLOSE TO THE STEPS WHICH IMPEDES |
| | ACCESS TO AND FROM THE ACCESSIBLE PARKING SPACES. PER |
| | SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE ACCESSIBLE |
| | PARKING SPACES ARE TO BE LOCATED ON THE SHORTEST |
| | POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN |
| | ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN OF |
| | ACCESSIBLE PARKING |
| | SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA |
| | ACCESSIBILITY CODE |
| | |
| | 3. SHEET A1.0 SITE PLAN. NEITHER OF THE ACCESSIBLE |
| | PARKING SPACES IS CALLED OUT AS VAN ACCESSIBLE. PER |
| | SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN |
| | EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN |
| | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY |
| | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT |
| | SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 4. SHEET A1.0 SITE PLAN. THE EXIT DISCHARGE DOOR FROM |
| | THE WEST STAIR DISCHARGES INSIDE THE BUILDING. PER |
| | SECTION 1027.1 OF FLORIDA BUILDING CODE, THE EXIT |
| | DISCHARGE DOOR SHALL DISCHARGE DIRECTLY TO THE OUTSIDE |
| | SO THAT USERS DO NOT RE-ENTER A FIRE RISK AREA WHEN |
| | LEAVING THE STAIR ENCLOSURE. |
| | |
| | 5. SHEET A2.5 LEVEL 6 ROOF PLAN. ONLY ONE EXIT STAIR IS |
| | SHOWN SERVING THE ROOF GARDEN/DECK. PER SECTION 1021.1 |
| | OF FLORIDA BUILDING CODE, TWO EXITS ARE REQUIRED. |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |