Plan Review Notes
Plan Review Notes For Project Z14010020
Project Number Z14010020
Review Stop PU
Sequence Number 1
Notes
Date Text
2014-02-11 16:12:55JLOEBIG
  
 THE NUMBER OF SANITARY SEWER LATERALS IS STILL THREE
 (3). THE 4" SANITARY LINE SHOULD BE CUT AND CAPPED IF
 THE LARGER 6" LINE IS PREFERRED (PALM BEACH LAKES
 FACING BUILDING) AND THE LOCATION OF SANITARY
 CLEAN-OUTS SHOULD BE INDICATED.
  
 THERE ARE TWO (2) 2" WATER METERS AVAILABLE, WILL THE
 TWO BUILDINGS CONTINUE TO BE SERVICED BY BOTH METERS?
 PLANS SHOW EXISTING UTILITES, HOWEVER THERE WAS NO
 INDICATION WHICH WOULD ACTUALLY BE UTILIZED.
  
  
  
  
 JACKSON LOEBIG
 O&M SUPERINTENDENT