| 2014-02-12 11:23:34 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. SHEET A100 SITE PLAN. THE ACCESSIBLE PARKING SPACES |
| | ARE NOT THE CLOSEST PARKING SPACES TO THE BUILDING |
| | ENTRANCE. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY |
| | CODE ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE |
| | SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING |
| | TO AN ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN |
| | OF ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION |
| | 502 OF FLORIDA ACCESSIBILITY CODE |
| | |
| | 3. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDING |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE |
| | |
| | 4. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 5. SHEET A202 3RD FLOOR PLAN AND SHEET A602 3D VIEWS. |
| | THE ROOF PATIO IS SHOWN WITH NO EXITS. PER SECTION |
| | 1021.1 OF FLORIDA BUILDING CODE, TWO EXITS ARE REQUIRED |
| | IF THIS AREA IS USED AS A PATIO. |
| | |
| | 6. SHEET A206 9TH FLOOR PLAN PENTHOUSE. THE POOL IS |
| | SHOWN WITH ONE EXIT AND AN INSWING DOOR. PER SECTION |
| | 1021.1 OF FLORIDA BUILDING CODE, THE POOL SHALL HAVE |
| | TWO EXITS AND THE DOORS SHALL SWING IN THE |
| | DIRECTION OF EGRESS. |
| | |
| | 7. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE |
| | OBTAINED BEFORE COMMENCING THE WORK. |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |