| 2014-01-23 14:31:51 | 2ND REVIEW RESPONSE |
| | |
| | AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED |
| | JANUARY 21, 2014, FROM URBAN DESIGN KILDAY STUDIOS, TO |
| | ERIC SCHNEIDER, PRINCIPAL PLANNER, THE PREVIOUSLY |
| | SUBMITTED FIRE PREVENTION BUREAU COMMENTS HAVE BEEN |
| | ADDRESSED. |
| | |
| | THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES |
| | NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT |
| | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |
| | |
| 2014-01-06 14:03:02 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | 1. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 2. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE |
| | DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF |
| | POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 3. ALL CONSTRUCTION SHALL COMPLY WITH THE FLORIDA FIRE |
| | PREVENTION CODE, 2010 EDITION, INCLUDING BUT NOT |
| | LIMITED TO, CHAPTER 14, NEW EDUCATIONAL OCCUPANCIES. |
| | |
| | 4. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS |
| | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, |
| | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY |
| | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 5. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS |
| | STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE |
| | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION |
| | BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 6. A NFPA 72 COMPLIANT FIRE ALARM SYSTEM IS REQUIRED |
| | FOR THIS STRUCTURE. |
| | |
| | 7. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY |
| | WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS. |
| | EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS |
| | SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. |
| | |
| | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| | ON THE PLAN. THE FIRE HYDRANTAND FDC'S FOR THIS PROJECT |
| | SHALL BE CLOSELY COORDINATED WITH THE BUREAU OF FIRE |
| | PREVENTION. IT WILL RECOMMENDED THAT THE PROPOSED NEW |
| | HYDRANT LOCATIONS BE MOVED CLOSER TO THE BUILDING IN AN |
| | AGREEABLE LOCATION. |
| | |
| | 9. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL BE |
| | PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY |
| | EQUIPMENT. |
| | |
| | 10. ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND |
| | HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN |
| | THE DOOR SCHEDULE. |
| | |
| | 11. PRESCRIPTIVE STRENGTH REQUIREMENTS FOR ALL |
| | HANDRAILS AND GUARDRAILS FOR THE BUILDING SHALL BE |
| | PROVIDED AND CLEARLY INDICATED. |
| | |
| | 12. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY |
| | ILLUSTRATED ON THE PLAN. |
| | |
| | 13. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING |
| | EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN. |
| | |
| | 14. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE |
| | CLEARLY IDENTIFIED AND INDICATED ON THE PLAN. |
| | |
| | 15. STAIR DETAIL SHALL BE PROVIDED INCLUDING MINIMUM |
| | RISE, RUN, AND TREAD DEPTH. |
| | |
| | 16. NOTICE REQUIRED FOR STRUCTURES WITH LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR |
| | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR |
| | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE |
| | PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY |
| | DOOR. |
| | |
| | 17. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS |
| | BUILDING. |
| | |
| | 18. BUILDING ADDRESSES ARE REQUIRED ON THE BUILDING. |
| | THE ADDRESS IS TO BE A MINIMUM OF AT LEAST 6" HIGH AND |
| | CONTRAST TO THE BACKGROUND THAT THEY ARE AFFIXED. |
| | |
| | 19. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | 20. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| | PLANS IN ACCORDANCE WITH THE REQUIREMENTS OF ALL |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| |