| Plan Review Notes For Project Z13120013 |
| Project Number |
Z13120013 |
|
| Review Stop |
STORM |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-03 17:11:39 | 1. DRAINAGE DESIGN TO MEET SFWMD CRITERIA. | | | 2. PROVIDE COPY OF FDOT PERMIT BEFORE START OF | | | CONSTRUCTION. | | | 3. PROVIDE COPY OF PALM BEACH COUNTY RIGHT-OF-WAY | | | PERMIT BEFORE START OF CONSTRUCTION. | | | 4. PROVIDE SIGNED AND SEALED SWPPP AND FINAL PGD PLANS | | | WITH ENGINEERING PERMIT APPLICATION. | | | 5. PROVIDE SIGNED AND SEALED DRAINAGE CALCULATIONS WITH | | | ENGINEERING PERMIT APPLICATION. | | | 6. VERTICAL DATUM ON SURVEY AND ENGINEERING PLANS NEEDS | | | TO BE NGVD 1929. | | | 7. INDICATE CONTROL STRUCTURE LOCATION FOR DRAINAGE | | | SYSTEM. | | | 8. SHOW LOCATIONS OF DOWN SPOUTS CONNECTING INTO | | | DRAINAGE SYSTEM. DOWN SPOUTS SHOULD CONNECT DIRECTLY | | | INTO CATCH BASINS OR DRAINAGE MANHOLES WHERE EVER | | | POSSIBLE. | | | 9. SHOW ALL PROPOSED AND EXISTING UTILITIES ON | | | LANDSCAPE PLANS. DRAINAGE IS NOT SHOWN. | | | 10. VERIFY OWNERSHIP OF EXISTING SANITARY SEWER SYSTEM | | | THAT IS BEING CONNECTED TO. WILL EASEMENT BE NEEDED FOR | | | LATERAL CONNECTION OUTSIDE THE APPLICANT'S PROPERTY? | | | 11. AVOID PLANTING TREES WITHIN 5 FEET OF UNDERGROUND | | | UTILITIES. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING AND PUBLIC WORKS DEPARTMENT | | | 561-494-1120 | | | |
| |