| 2014-01-06 11:48:43 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | 1. ALL CONSTRUCTION SHALL COMPLY WITH THE FLORIDA FIRE |
| | PREVENTION CODE, 2010 EDITION, INCLUDING BUT NOT |
| | LIMITED TO, CHAPTER 12, NEW ASSEMBLY OCCUPANCIES. |
| | |
| | 2. ALL ADDITIONS OR DELETIONS TO THE EXISTING FIRE |
| | ALARM AND SPRINKLER SYSTEMS SHALL BE DONE BY A SYSTEM |
| | CERTIFIED LICENSED CONTRACTOR. THOSE PERMITS SHALL BE |
| | SHOP DRAWING APPLIED FOR SEPARATELY. |
| | |
| | 3. COMPLETE LIFE SAFETY PLANS FOR THE PROJECT SHALL BE |
| | PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY |
| | EQUIPMENT. |
| | |
| | 4. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY |
| | WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS. |
| | EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS |
| | SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. |
| | |
| | 5. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES |
| | NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | 6. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS |
| | IN ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE |
| | CODES AND STANDARDS. |
| | |
| | |
| | |
| | |
| | |
| |