| 2013-12-05 15:52:59 | THE FOLLOWING COMMENTS ARE PROVIDED BY PETER LEDUC, |
| | FIRE MARSHAL. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE |
| | DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF |
| | POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 3. TOWNHOMES ARE CONSIDERED APARTMENTS. ALL APARTMENT |
| | BUILDINGS SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION |
| | CODE, 2010 EDITION, THE LIFE SAFETY CODE, 2009 EDITION, |
| | INCLUDING MORE SPECIFICALLY, CHAPTER 30, NEW |
| | APARTMENTS. |
| | |
| | 4. A NFPA 13R COMPLAINT FIRE SPRINKLER SYSTEM IS |
| | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, |
| | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY |
| | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 5. SMOKE ALARMS ARE REQUIRED IN EVERY SLEEPING ROOM AND |
| | OUTSIDE OF THE SLEEPING ROOMS AND IN ALL LEVELS OF THE |
| | DWELLING UNITS. THESE DETECTORS SHALL BE HARD WIRED AND |
| | SHALL BE INTERCONNECTED TO ONE ANOTHER. |
| | |
| | 6. INTERIOR FINISH CLASSIFICATIONS FOR ALL WALLS AND |
| | CEILINGS SHALL BE CLEARLY INDICATED ON THE SUBMITTED |
| | BUILDING PERMIT PLAN. |
| | |
| | 7. BUILDING ADDRESSES ARE REQUIRED ON THE BUILDING. THE |
| | ADDRESS IS TO BE A MINIMUM OF AT LEAST 6" HIGH AND |
| | CONTRAST TO THE BACKGROUND THAT THEY ARE AFFIXED. |
| | |
| | 8. STAIR DETAIL SHALL BE PROVIDED INCLUDING MINIMUM |
| | RISE, RUN, AND TREAD DEPTH. |
| | |
| | 9. REQUIRED FIRE SEPARATIONS BETWEEN EACH APARTMENT |
| | AND/OR TENANT SHALL BE CLEARLY INDICATED AND |
| | ILLUSTRATED ON THE BUILDING PLAN. |
| | |
| | 10. A STATE OF FLORIDA COMPLIANT TRUSS ROOF & FLOOR |
| | ASSEMBLY SIGN IS REQUIRED FOR THIS STRUCTURE. STRUTURES |
| | WITH LIGHT-FRAME TRUSS FLOOR AND ROOF SYSTEMS SHALL BE |
| | MARKED WITH THE LETTERS "R/F". THE APPROVED SYMBOL |
| | SHALL BE PLACED ON ONE SIDE ONLY AND SPACED NOT CLOSER |
| | THAN 100 FEET OR AT EACH END OF THE STRUCTURE WHEN SUCH |
| | STRUCTURE IS LESS THAN 100 FEET IN LENGTH. |
| | |
| | |
| | |
| |