Plan Review Notes
Plan Review Notes For Project Z13110009
Project Number Z13110009
Review Stop STORM
Sequence Number 2
Notes
Date Text
2013-12-23 13:54:431. COMMENTS 2, 8, 9 AND 10 FROM FIRST REVIEW STILL
 OUTSTANDING.
 2. INCLUDE LATEST SURVEY IN THE ARCHITECTURAL SET OF
 PLANS.
 3. AVOID PLANTING TREES WITHIN 5 FEET OF UTILITIES.
 4. ON CONCEPTUAL SITE ENGINEERING PLAN, THERE IS AN
 EXISTING CB EAST OF SURVEY LINE L4 NOTED TO REMAIN. IT
 APPEARS THIS CB IS WITHIN THE PAVED VALET ENTRANCE RAMP
 THAT WILL BE AT 10% SLOPE.
 5. THE HANDRAILS OF THE CONCRETE RAMPS ON BOTH SIDES OF
 THE HOTEL ENTRANCE SHOULD NOT PROTRUDE OVER THE
 SIDEWALK/WALKWAY ALONG THE STREET OR SEAWALL.
 6. RELOCATE SANITARY SEWER MAIN FROM UNDER THE PROPOSED
 RETAINING WALL OF PARKING LOT.
 7. PROVIDE INVERT ELEVATIONS FOR EXISTING SANITARY
 SEWER MANHOLE APPROXIMATELY 162 LF NORTH OF PROPOSED
 SANITARY MANHOLE #3.
 8. SLOPE IS FLAT FOR THE EXISTING 18" SANITARY SEWER
 PIPE BETWEEN MH8 AND MH10 ON BOUNDARY SURVEY SHEET.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT