| Plan Review Notes For Project Z13110009 |
| Project Number |
Z13110009 |
|
| Review Stop |
STORM |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-12-23 13:54:43 | 1. COMMENTS 2, 8, 9 AND 10 FROM FIRST REVIEW STILL | | | OUTSTANDING. | | | 2. INCLUDE LATEST SURVEY IN THE ARCHITECTURAL SET OF | | | PLANS. | | | 3. AVOID PLANTING TREES WITHIN 5 FEET OF UTILITIES. | | | 4. ON CONCEPTUAL SITE ENGINEERING PLAN, THERE IS AN | | | EXISTING CB EAST OF SURVEY LINE L4 NOTED TO REMAIN. IT | | | APPEARS THIS CB IS WITHIN THE PAVED VALET ENTRANCE RAMP | | | THAT WILL BE AT 10% SLOPE. | | | 5. THE HANDRAILS OF THE CONCRETE RAMPS ON BOTH SIDES OF | | | THE HOTEL ENTRANCE SHOULD NOT PROTRUDE OVER THE | | | SIDEWALK/WALKWAY ALONG THE STREET OR SEAWALL. | | | 6. RELOCATE SANITARY SEWER MAIN FROM UNDER THE PROPOSED | | | RETAINING WALL OF PARKING LOT. | | | 7. PROVIDE INVERT ELEVATIONS FOR EXISTING SANITARY | | | SEWER MANHOLE APPROXIMATELY 162 LF NORTH OF PROPOSED | | | SANITARY MANHOLE #3. | | | 8. SLOPE IS FLAT FOR THE EXISTING 18" SANITARY SEWER | | | PIPE BETWEEN MH8 AND MH10 ON BOUNDARY SURVEY SHEET. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING AND PUBLIC WORKS DEPARTMENT | | | 561-494-1120 |
| |