2014-01-06 10:49:41PROJECT IS PASSED WITH LISTED PROVISIONS REQUIRING
 ATTENTION:
  
 1. RESTAURANT IS OUTLINED IN PLANS HOWEVER NO
 ACCOMMODATION IS PROVIDED FOR OIL/GREASE/WATER
 SEPARATOR.
  
 2. SANITARY SEWER CLEAN-OUT APPEARS NON-ACCESSIBLE IN
 LOCATION BEHIND ARCHITECTURAL KNEE-WALL FACING FLAGLER
 AVENUE.
  
 3. PROPOSED RELOCATION OF 18? PVC SANITARY SEWER MAIN
 SHOWS THREE (3) NEW MANHOLES WITHOUT THE NECESSARY
 INFORMATION FOR RIM AND INVERT ELEVATIONS. A FOURTH
 MANHOLE IS PROPOSED TO REPLACE AN EXISTING MANHOLE
 (SSMH7889), HOWEVER THE PROPOSED NORTH INVERT
 (DOWNHILL) ELEVATION IS (-) 3.46 AND THE PRECEDING
 UPHILL 70 FEET OF SANITARY MAIN IS ONLY (-) 3.49.
  
  
  