| 2013-12-11 12:23:06 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. THE PROPOSED BUILDING WILL BE IN FLOOD ZONE A5 FOR |
| | WHICH THE BASE FLOOD ELEVATION IS EL 7 NGVD. THE |
| | ELEVATION OF THE FIRST FLOOR OF THE BUILDING AND ALL |
| | ASSOCIATED MECHANICAL EQUIPMENT (CHILLERS, GENERATORS |
| | ETC.) SHALL BE 6 INCHES (FREEBOARD) ABOVE THAT BASE |
| | FLOOD ELEVATION. |
| | |
| | 3. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT |
| | LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS |
| | 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE |
| | PUBLIC RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR |
| | FACILITY ENTRANCES. |
| | |
| | 4. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT |
| | LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS |
| | 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, |
| | CONNECTING ACCESSIBLE BUILDING OR FACILITY ENTRANCES |
| | WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE |
| | BUILDING OR FACILITY |
| | |
| | 5. ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER |
| | THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY |
| | WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 6. THE PARKING GARAGE APPEARS TO BE FOR VALET USE ONLY. |
| | THOSE ARE COVERED/SHELTERED PARKING SPACES, THEREFORE |
| | SOME COVERED/SHELTERED ACCESSIBLE PARKING SPACES MUST |
| | BE PROVIDED FOR EQUIVALENT FACILITATION. PLEASE NOTE |
| | THAT NOT ALL VEHICLES MODIFIED FOR ACCESSIBILITY CAN BE |
| | OPERATED BY A VALET. PER SECTION 208.3 OF FLORIDA |
| | ACCESSIBILITY CODE ACCESSIBLE PARKING SPACES ARE TO BE |
| | LOCATED ON THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM |
| | ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE FOR EACH |
| | BUILDING. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL |
| | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE |
| | |
| | 7. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, |
| | ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A |
| | PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND |
| | DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 8. THE TYPE OF CONSTRUCTION FOR THE BUILDINGS SHALL BE |
| | IN ACCORDANCE WITH THE HEIGHT, AREA AND OCCUPANCY |
| | LIMITATIONS IN CHAPTER 5 OF THE FLORIDA BUILDING CODE |
| | |
| | 9. COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE |
| | OF OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF |
| | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE |
| | VERIFIED. |
| | |
| | 10. ENCLOSED PARKING GARAGES MUST HAVE EXHAUST SYSTEMS |
| | DESIGNED TO MINIMIZE NOISE LEVELS USING INLINE FAN |
| | SILENCERS OR OTHER APPROVED METHODS. |
| | |
| | 11. ALL APPLICABLE PERMITS MUST BE OBTAINED BEFORE |
| | COMMENCING THE WORK. |
| | |
| | 14. FOR STREET ADDRESSING CONTACT JAMES JUDGE, GIS |
| | COORDINATOR, AT (561) 822 1226 |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |