| 2013-10-08 14:05:11 | 1. THE REVIEW FOR THE AMENDMENT TO THE FSPR 06-16 WILL |
| | BE CONDUCETED BASED ON THE 1994 DMP REGULATIONS. |
| | 2. PLEASE CONFIRM COMPLIANCE WITH THE 40 FEET MINIMUM |
| | DISTANCE FROM THE CENTER LINE OF THE ROAD TO THE |
| | BUILDING FACE. |
| | 3. PLEASE CONFIRM COMPLIANCE WITH THE MINIMUM 20 FEET |
| | RECESS LINE ALONG MINIMUM 80% OF BUILDING FRONTAGE. |
| | 4. PLEASE CONFIRM COMPLIANCE WITH MINIMUM 10 FEET REAR |
| | RECESS LINE ABOVE 80 FEET IN HEIGHT. |
| | 5. PROPOSED FINISHED FLOOR TO FINISHED FLOOR ON 1ST |
| | FLOOR EXCEED MAXIMUM 20' ALLOWED. |
| | 6. PROPOSED 2ND AND 3RD FLOOR EXCEED THE MAXIMUM 18' |
| | FINISHED FLOOR TO FINISHED FLOOR ALLOWED. |
| | 7. PROPOSED PARKING GARAGE ON DIXIE HWAY IS EXPOSED, |
| | THEREFORE ALL PARKING LEVELS WILL BE COUNTED AS A |
| | FLOOR. PROPOSED BUILDING WILL EXCEED MAXIMUM NUMBER OF |
| | FLOORS PERMITTED. |
| | 8. TRANSITION LINE SHALL BE PROVIDED AT THE TOP OF THE |
| | 2ND STORY. |
| | 9. ACTIVE USES ALONG FERN STREET SHALL BE MINIMUM 20' |
| | IN DEPTH. |
| | 10. VEHICULAR ENTRIES SHALL BE MAXIMUM 20' IN WIDTH. |
| | 11. PLEASE CONFIRM COMPLIANCE WITH MINIMUM 20% AND |
| | MAXIMUM 45% GLAZED AREA OF FACADE. |
| | 12.PLEASE CONFIRM COMPLIANCE WITH REQUIRED 70% GLAZED |
| | STOREFRONT ON THE 1ST FLOOR FOR RETAIL AREA. |
| | 13. WINDOWS SHALL BE RECESSED MINIMUM 2" FROM EXTERIOR |
| | FACE. |
| | 14. AS PROPOSED PROJECT WILL REQUIRED 62,500SF |
| | TRANSFERED FROM THE PARK, AND 142,496SF FROM OTHER TDR |
| | SOURCES. |
| | 15. SIDEWALK SHALL BE CONCRETE. |
| | 16. TREE GRATES SHALL BE CITY STANDARD, AND SHALL BE |
| | INSTALL EVERY 30 FEET ALONG THE CURB. TREES SHALL BE |
| | LIVE OAKS. |
| | 17. CITY STANDARD STREET LIGHT FIXTURES SHALL BE |
| | INSTALLED ALONG THE FRONTAGE LINE. |
| | 18. SOME DOORS ALONG FERN STREET ARE ENCROACHING THE |
| | ROW. DOORS SHALL BE RECCESSED. |
| | 19. PLEASE PROVIDE AUTO TURN TO CONFIRM CIRCULATION OF |
| | DROP-OFF AREA. |
| | 20. COLOR ELEVATIONS AND RENDERS WILL BE REQUIRED FOR |
| | FURTHER REVIEW. |
| | 21. CIVIL DRAWINGS DO NOT ACCURATELY REFLECT THE STREET |
| | CONDITIONS. |
| | 22. HOW IS THE TRASH PICK UP? PRIVATE? |
| | 23. SOME PARKING SPACES ON WEST SIDE DO NOT MEET |
| | MINIMUM DIMENSIONS. INCLUDE DIMENSIONS. |
| | 24. PLEASE CONSIDER THE RELOCATION OF THE TRAFFIC |
| | SIGNAL BOX AT THE DIXIE HWAY AND FERN STREET CORNER. |
| | 25. ANY UTILITY EQUIPMENT (SUCH AS BACK FLOW |
| | PREVENTORS) SHALL BE LOCATED OUTSIDE THE ROW AND/OR |
| | REQURIED FRONT SETBACK. |
| | 26. ARE THE EXISTING UTILITY LINES ALONG THE ALLEY |
| | PROPOSED FOR RELOCATION OR UNDERGROUND? |
| | 27. PROPOSED BLANK WALL ON THE EAST AND NORTH ELEVATION |
| | WILL HAVE A GREAT IMPACT ON THE SURROUNDING. |
| | ARCHITECURAL TREATMENT SHALL BE INCORPORATED TO THE |
| | EAST ELEVATION, AND OPENNIGNS SHALL BE INTRODUCED TO |
| | THE NORTH ELEVATION. |
| | 28. SURVEY SHALL INCLUDE DIMENSION OF EXISTING SIDEWALK |
| | AND PAVEMENT AREA. |