| 2013-10-30 14:23:39 | THE CONCERNS OF THE BUREAU OF FIRE PREVENTION HAVE BEEN |
| | ADDRESSED. |
| | |
| | FURTHER REVIEW AND COMMENT IS RESERVED FOR ANY CHANGES |
| | TO THE PROPOSED PROJECT OR THE SUBMITTAL OF THE |
| | OFFICIAL CONSTRUCTIONS PLANS. |
| 2013-10-02 17:30:10 | FIRE RESCUE COMMENTS |
| | |
| | CENTRAL PARK PLAZA |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE |
| | DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF |
| | POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 4. ALL APARTMENT BUILDINGS SHALL COMPLY WITH THE |
| | FLORIDA FIRE PREVENTION CODE, 2010 EDITION, THE LIFE |
| | SAFETY CODE, 2009 EDITION, INCLUDING MORE SPECIFICALLY, |
| | CHAPTER 30, NEW APARTMENTS. |
| | |
| | 5. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, |
| | PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE, |
| | INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE |
| | OCCUPANCIES (PARKING STRUCTURES) |
| | |
| | 6. SMOKE ALARMS ARE REQUIRED IN EVERY SLEEPING ROOM AND |
| | OUTSIDE OF THE SLEEPING ROOMS AND IN ALL LEVELS OF THE |
| | DWELLING UNITS. THESE DETECTORS SHALL BE HARD WIRED AND |
| | SHALL BE INTERCONNECTED TO ONE ANOTHER. |
| | |
| | 7. INTERIOR FINISH CLASSIFICATIONS FOR ALL WALLS AND |
| | CEILINGS SHALL BE CLEARLY INDICATED ON THE SUBMITTED |
| | BUILDING PERMIT PLAN. |
| | |
| | 8. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA |
| | 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS |
| | STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE |
| | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION |
| | BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 9. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS |
| | STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE |
| | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION |
| | BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 10. ALL VERTICAL AND HORIZONTAL FIRE SEPARATIONS FOR |
| | THIS BUILDING SHALL BE CLEARLY IDENTIFIED AND |
| | INDICATED. |
| | |
| | 11. ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND |
| | HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN |
| | THE DOOR SCHEDULE. |
| | |
| | 12. PRESCRIPTIVE STRENGTH REQUIREMENTS FOR ALL |
| | HANDRAILS AND GUARDRAILS FOR THE BUILDING SHALL BE |
| | PROVIDED AND CLEARLY INDICATED. |
| | |
| | 13. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY |
| | ILLUSTRATED ON THE PLAN. |
| | |
| | 14. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING |
| | EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN. |
| | |
| | 15. BUILDING ADDRESSES ARE REQUIRED ON THE BUILDING. |
| | THE ADDRESS IS TO BE A MINIMUM OF AT LEAST 6" HIGH AND |
| | CONTRAST TO THE BACKGROUND THAT THEY ARE AFFIXED. |
| | |
| | 16. FLAME SPREAD DETAILS ON ALL FOAM BACKED STUCCO TRIM |
| | PLANNED FOR BUILDING SHALL BE PROVIDED FOR AND/OR |
| | IDENTIFIED AND INDICATED ON THE PLAN. |
| | |
| | 17. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE |
| | CLEARLY IDENTIFIED AND INDICATED ON THE PLAN. |
| | |
| | 18. STAIR DETAIL SHALL BE PROVIDED INCLUDING MINIMUM |
| | RISE, RUN, AND TREAD DEPTH. |
| | |
| | 19. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS |
| | BUILDING. |
| | |
| | 20. TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT |
| | DOORS. |
| | |
| | 21. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL |
| | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY |
| | EQUIPMENT. |
| | |
| | 22. OCCUPANT LOADS FOR ASSEMBLY SPACES SHALL BE |
| | DETERMINED BY THE BUREAU OF FIRE PREVENTION AND ARE |
| | REQUIRED TO BE POSTED. |
| | |
| | 23. THE FIRE RATING OF ALL SHAFTS SHALL BE CLEARLY |
| | INDICATED ON THE BUILDING PLAN. |
| | |
| | 24. REQUIRED FIRE SEPARATIONS BETWEEN EACH APARTMENT |
| | AND/OR TENANT SHALL BE CLEARLY INDICATED AND |
| | ILLUSTRATED ON THE BUILDING PLAN. |
| | |
| | 25. REQUIRED CORRIDOR FIRE RATING SHALL BE CLEARLY |
| | INDICATED AND ILLUSTRATED ON THE BUILDING PLAN. |
| | |
| | 26. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF |
| | FIRE PREVENTION. |
| | |
| | 27. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS |
| | (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND |
| | COORDINATED WITH THE BUREAU OF FIRE PREVENTION. |
| | |
| | 28. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE |
| | ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED |
| | ON THE PLAN. |
| | |
| | 29. ANNUALLY, EMERGENCY INSTRUCTIONS ARE TO BE PROVIDED |
| | TO EACH APARTMENT AND/OR TENANT. THESE INSTRUCTIONS ARE |
| | TO INDICATE THE LOCATION OF ALARMS, EGRESS PATHS, AND |
| | ACTIONS TO BE TAKEN IN THE EVENT OF A FIRE OR TO AN |
| | ALARM ACTIVATION. |
| | |
| | 30. ALL DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS |
| | SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE EQUIPPED |
| | WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR TO |
| | POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL BE |
| | CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR SCHEDULE. |
| | |
| | 31. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE BUILDING |
| | REACHES THREE LEVEL OR THIRTY FEET WHILE BEING |
| | CONSTRUCTED. |
| | |
| | DENIED |
| | |
| | PETER LEDUC, BATTALION CHIEF, FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |
| | |
| | |
| | |
| |