| 2013-10-09 09:58:22 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER |
| | THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY |
| | WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 3. ACCESSIBLE PARKING SPACES. TO COMPLY WITH FAIR |
| | HOUSING ACT, AND FLORIDA ACCESSIBILITY CODE, THE |
| | PARKING TABLE ON SHEET SP-1 CORRECTLY STATES THAT 8 |
| | ACCESSIBLE SPACES ARE REQUIRED. THE ONLY ACCESSIBLE |
| | PARKING SPACES THAT CURRENTLY APPEAR TO BE SHOWN ON THE |
| | PLANS ARE THE 4 SHOWN ON SHEET A-1 FIRST FLOOR PLAN. |
| | PLEASE SHOW THE LOCATION OF ALL 8 ACCESSIBLE PARKING |
| | SPACES. SEE TABLE 208.2 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 4. LOCATION OF ACCESSIBLE PARKING SPACES. SHEET A-1 |
| | FIRST FLOOR PLAN. TO ACCESS THE BUIDING FROM THE |
| | ACCESSIBLE PARKING SPACES, THE USER IS COMPELLED TO |
| | CROSS THE VEHICULAR TRAVEL LANES RIGHT BY THE ENTRANCE |
| | TO THE PARKING GARAGE. AT THAT LOCATION, THE VEHICULAR |
| | TRAVEL LANES WILL HAVE THE GREATEST TRAFFIC FLOW. |
| | PLEASE CONSIDER WHETHER THIS IS THE BEST LOCATION FOR |
| | ACCESSIBLE PARKING SPACES. |
| | |
| | 4. VAN ACCESSIBLE PARKING SPACES. THE PARKING TABLE ON |
| | SHEET SP-1 CORRECTLY STATES THAT 2 VAN ACCESSIBLE |
| | SPACES ARE REQUIRED. THE ONLY VAN ACCESSIBLE PARKING |
| | SPACE THAT CURRENTLY APPEARS TO BE SHOWN ON THE PLANS |
| | IS THE ONE SHOWN ON SHEET A-1 FIRST FLOOR PLAN. PLEASE |
| | SHOW THE LOCATION OF BOTH VAN ACCESSIBLE PARKING |
| | SPACES. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY |
| | CODE, ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) |
| | IN A PARKING STRUCTURE, SHALL BE "VAN ACCESSIBLE: AND |
| | DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICLULAR ACCESS ROUTE) |
| | |
| | 5. COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE |
| | OF OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF |
| | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE |
| | VERIFIED. |
| | |
| | 6. ENCLOSED PARKING GARAGES MUST HAVE EXHAUST SYSTEMS |
| | DESIGNED TO MINIMIZE NOISE LEVELS USING INLINE FAN |
| | SILENCERS OR OTHER APPROVED METHODS. |
| | |
| | 7. STAIR 04 EXIT DOOR. SHEET A-1 FIRST FLOOR PLAN. |
| | STAIR 04 IS CURRENTLY SHOWN WITH NO EXIT DOOR TO THE |
| | SIDEWALK AT FIRST FLOOR LEVEL. |
| | |
| | 8. STAIR 03 IN AMENITY ROOM ADJACENT TO THE VALET |
| | STATION. SHEET A-1 FIRST FLOOR PLAN. STAIR 03 DOES NOT |
| | APPEAR IN THE SECOND FLOOR PLAN, SO IT DOES NOT LEAD TO |
| | ANYWHERE, UNLESS A BASEMENT LEVEL IS PROPOSED. |
| | |
| | 9. ALL APPLICABLE PERMITS MUST BE OBTAINED BEFORE |
| | COMMENCING THE WORK. |
| | |
| | 10. FOR STREET ADDRESSING CONTACT JOSH MILLS, GIS |
| | SUPPORT SPECIALIST ON 561 494 1084 |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |