Plan Review Notes
Plan Review Notes For Project Z13080024
Project Number Z13080024
Review Stop STORM
Sequence Number 2
Notes
Date Text
2013-10-01 01:34:041. STORM DRAINAGE CONNECTIONS NEED TO BE CLARIFIED FOR
 THE FIRST PROPOSED ONSITE MANHOLE FOR THE CITY'S
 DRAINAGE SYSTEM THROUGH THE SITE (THE MANHOLE EAST OF
 THE DRIVEWAY LANDSCAPE ISLAND. IT APPEARS THERE IS A
 PIPE COMING DUE SOUTH OUT OF THE MANHOLE AND CONNECTING
 TO AN INLET ALONG THE WEST PROPERTY LINE. FROM THIS
 INLET, THERE IS A PIPE TO THE SOUTHEAST THAT CONNECTS
 TO A PROPOSED STORM MANHOLE. THE STORM MANHOLE HAS
 PROPOSED EXFILTRATION TRENCH SOUTH OF THE MANHOLE. THE
 DRAINAGE SYSTEM THEN TURNS TO THE EAST AND CONNECTS TO
 AN EXISTING OUTFALL JUST TO THE EAST-SOUTHEAST OF TOWER
 3. THUS IT APPEARS FROM THE INITIAL MANHOLE IN THE
 DRIVEWAY, WATER CAN FLOW SOUTH THEN EAST TO THE OUTFALL
 SOUTH OF TOWER 3 OR CONTINUE EAST OUT OF THE MANHOLE TO
 THE EXISTING 66" OUTFALL NORTHEAST OF THE EXISTING
 RESTAURANT. THE SOUTH CONVEYANCE WILL BYPASS THE
 PROPOSED POLLUTANT RETARDANT BASIN ON THE 66" OUTFALL
 PIPE.
 2. PERMITS FROM SFWMD AND/OR FDEP WILL BE NEEDED FOR
 THE SITE DRAINAGE SYSTEM AND THE CHANGES TO THE OUTFALL
 PIPE SIZES.
 3. PREVIOUS COMMENTS TO BE ADDRESSED IN LATER
 DEVELOPMENT PROCESS SUBMITTALS TO THE CITY.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120
  