Plan Review Notes
Plan Review Notes For Project Z13080024
Project Number Z13080024
Review Stop B
Sequence Number 1
Notes
Date Text
2013-09-11 09:28:30DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. IT IS NOTED THAT THE PLANS ARE VERY PRELIMINARY AT
 THIS STAGE AND ARE NOT INTENDED TO SPECIFICALLY ADDRESS
 BUILDING CODE REQUIREMENTS YET. THIS REVIEW IS A
 CURSORY REVIEW AS IT RELATES TO THE SITE. IT IS NOT A
 REVIEW FOR FULL COMPLIANCE WITH FLORIDA BUILDING CODE.
 THE FOLLOWING COMMENTS ARE TO BE ADDRESSED FOR
 PERMITTING.
  
 2. THE PROPOSED BUILDING WILL BE IN A FLOOD ZONE. THE
 LOWEST FLOOR OF THE BUILDINGS AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE EITHER FLOODPROOFED OR ELEVATED TO 6 INCHES
 (FREEBOARD) ABOVE THE BASE FLOOD ELEVATION.
  
 3. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT
 LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS
 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE
 PUBLIC RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES.
  
 4. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT
 LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS
 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE,
 CONNECTING ACCESSIBLE BUILDING OR FACILITY ENTRANCES
 WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE
 BUILDING OR FACILITY
  
 5. ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER
 THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY
 WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE.
  
 6. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE
 ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE
 SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN
 OF ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION
 502 OF FLORIDA ACCESSIBILITY CODE
  
 7. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE,
 ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A
 PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND
 DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA
 ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98
 INCHES AT SPACE AND VEHICLE ACCESS ROUTE)
  
 8. THE TYPE OF CONSTRUCTION FOR THE BUILDINGS SHALL BE
 IN ACCORDANCE WITH THE HEIGHT, AREA AND OCCUPANCY
 LIMITATIONS IN CHAPTER 5 OF THE FLORIDA BUILDING CODE
  
 9. COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE
 OF OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 10. ENCLOSED PARKING GARAGES MUST HAVE EXHAUST SYSTEMS
 DESIGNED TO MINIMIZE NOISE LEVELS USING INLINE FAN
 SILENCERS OR OTHER APPROVED METHODS.
  
 11. ALL APPLICABLE PERMITS MUST BE OBTAINED BEFORE
 COMMENCING THE WORK.
  
 12. FOR STREET ADDRESSING CONTACT JOSH MILLS, GIS
 SUPPORT SPECIALIST ON 561 494 1084
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  