| Plan Review Notes For Project Z13080018 |
| Project Number |
Z13080018 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-04 08:52:06 | CONVENTION CENTER HOTEL AND GARAGE | | | | | | BUREAU OF FIRE PREVENTION | | | | | | THE PREVIOUSLY SUBMITTED COMMENTS HAVE BEEN ADDRESSED. | | | | | | THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES | | | NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS IN | | | ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE | | | CODES AND STANDARDS. | | | | | | PETER LEDUC | | | | | | BATTALION CHIEF, FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | | | 2013-09-06 16:06:18 | THIS SUBMITTAL IS QUITE DETAILED AND FURTHER REVEIW IS | | | NEEDED; HOWEVER, ACCESS AND EXITING POINTS APPEAR TO BE | | | IN ORDER. | | | | | | FURTHER REVIEW AND EVALUATION OF THE HYDRANT AND FDC | | | LOCATIONS, FD CONTROL ROOM IS NEEDED WITH INPUT FROM | | | OPERATIONAL PERSONNEL PRIOR TO FINAL APPROVAL. | | | | | | ALL LIFE AND FIRE SAFETY CONSTRUCTION SHALL BE IN | | | COMPLIANCE WITH THE CURRENT 2010 EDITION OF THE FLORIDA | | | FIRE PREVENTION CODE. | | | | | | SPRINKLER PROTECTION WITHIN THE PARKING GARAGE AND | | | STANDPIPE CONNECTIONS IN THE STAIRWELLS IS REQUIRED. | | | |
| |