2013-08-12 15:12:491. CIVIL PLANS NOT SIGNED AND SEALED.
 2. TEMPORARY STORMWATER POND TO BE SIZED TO PROVIDE
 REQUIRED MINIMUM WATER QUALITY TREATMENT.
 3. PROVIDE COPY OF SFWMD ERP PERMIT WITH ENGINEERING
 PERMIT APPLICATION.
 4. SIGNED AND SEALED ENGINEERING PLANS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
 5. STORM WATER POLLUTION PREVENTION PLAN TO BE
 SUBMITTED WITH THE ENGINEERING PERMIT APPLICATION.
  