2013-07-01 05:36:53INFORMAL SITE PLAN REVIEW 13-05 (Z13060012)
 GRIFFIN AUTO CARE
 SOUTHEAST CORNER OF OLD OKEECHOBEE ROAD AND WILKINS
 AVENUE
 PLANS AND PLATS REVIEW COMMITTEE (PPRC) FIRE RESCUE
 COMMENTS
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS A
 COMPLETE SET OF DRAWINGS WERE NOT SUBMITTED. ADDITIONAL
 COMMENTS CAN BE EXPECTED AT TIME OF PERMITTING.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. NEW BUILDING IS TO COMPLY WITH THE INDUSTRIAL
 OCCUPANCY CHAPTER OF THE FLORIDA FIRE PREVENTION CODE,
 2010 EDITION.
  
 3. PLEASE SUBMIT COMPLETE MECHANICAL, ELECTRICAL, AND
 PLUMBING PLANS FOR PERMIT.
  
 4. PLEASE DISPLAY ALL FIRE SAFETY EQUIPMENT ON THE
 PLANS. (EXIT SIGNS, EMERGENCY LIGHTS, PORTABLE FIRE
 EXTINGUISHERS, ETC)
  
 5. PLEASE INDICATE HOW WASTE OIL WILL BE STORED,
 HANDLED, AND COLLECTED.
  
 6. PLEASE DISPLAY BUILDING ADDRESS ON PLANS. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE REQUIRED.
  
 7. PLEASE INDICATE PROPOSED OCCUPANT LOAD FOR THE
 BUILDING. (MAXIMUM AMOUNT OF EMPLOYEES THAT WILL BE
 WORKING IN THE BUILDING)
  
 8. PLEASE PROVIDE DETAILS ON DOOR HARDWARE.
  
 9. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 DENIED
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE