2013-06-04 06:47:06PLANNING BOARD CASE NO 1557C (Z13050023)
 2101 OKEECHOBEE BOULEVARD
 ERIC SCHNEIDER, PRINCIPAL PLANNER
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS OTHER
 REQUIREMENTS MAY BE NECESSARY WHEN A COMPLETE SET OF
 PLANS ARE PROVIDED.
  
 1. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6"
 HIGH NUMBERS ARE REQUIRED AND SHALL CONTRAST TO THE
 BACKGROUND THEY ARE AFFIXED TO.
  
 2. STRUCTURES USED FOR PARKING SHALL COMPLY WITH NFPA
 88A AND NFPA 101, THE LIFE SAFETY CODE, 2009 EDITION
 (STORAGE, PARKING)
  
 3. PLEASE INDICATE THE LOCATIONS OF ALL EXIT SIGNS AND
 EMERGENCY LIGHTING EQUIPMENT.
  
 4. PLEASE INDICATE ALL VERTICAL AND HORIZONTAL FIRE
 SEPARATIONS.
  
 5. PLEASE INDICATE ON THE DRAWINGS THE LOCATIONS OF ALL
 EXITS AND EXIT DISCHARGE LOCATIONS.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY GATES.
 HOW DOES FIRE RESCUE ACCESS THROUGH THE SECURITY GATES.
  
 7. PLEASE PROVIDE A LIFE SAFETY PLAN ILLUSTRATING ALL
 EXITS, TRAVEL DISTANCES, OCCUPANT LOADS, ETC.
  
 8. PLEASE PROVIDE DETAILS ON ANY FIRE SPRINKLER OR FIRE
 ALARM SYSTEMS PLANNED FOR THE BUILDING.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE PROPOSED FUEL TANK.
  
 10. VEHICLES ON DISPLAY SHALL CONTAIN VERY LITTLE FUEL
 AND THE BATTERY TERMINALS SHALL BE DISCONNECTED.
  
 11. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 12. PLEASE SUBMIT COMPLETE PLANS TO THE CONSTRUCTION
 SERVICES DEPARTMENT FOR REVIEW.
  
 DENIED
  
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE