Plan Review Notes
Plan Review Notes For Project Z13050021
Project Number Z13050021
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-06-04 13:51:52PLANNING BOARD CASE NOS. 891U (Z13050021) AND 891V
 (Z13050022)
 1801 PALM BEACH LAKES BLVD.
 ERIC SCHNEIDER, PRINCIPAL PLANNER
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS OTHER
 REQUIREMENTS MAY BE NECESSARY WHEN A FULL SET OF
 DRAWINGS ARE PROVIDED.
  
 1. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING,
 AFTER CONSTRUCTION.
  
 2. PLEASE SUBMIT COMPLETE ARCHITECTURAL, MECHANICAL,
 ELECTRICAL, PLUMBING, FIRE SPRINKLER AND FIRE ALARM
 PLANS FOR REVIEW.
  
 3. PLEASE SUBMIT SEPARATE HOOD, DUCT, AND FIRE
 SUPPRESSION SYSTEM PLANS FOR ALL RESTAURANTS.
  
 4. BUILDING ADDRESSES REQUIRED. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS THAT CONTRAST WITH THE BACKGROUND THEY
 ARE AFFIXED TO,
  
 5. ALL CANOPIES THAT EXTEND OR COVER PEDESTRIANS ARE TO
 BE PROPERLY FIRE RETARDANT.
  
 6. TACTILE SIGNAGE REQUIRED ALL EXIT DOORS.
  
 7. PLEASE INDICATE ON THE PLANS ALL VERTICAL AND
 HORIZONTAL FIRE WALL SEPARATIONS.
  
 8. ALL LIGHTNING PROTECTION TO COMPLY WITH NFPA 780.
  
 9. NO STORAGE WILL BE PERMITTED IN ANY ELECTRICAL OR
 MECHANICAL ROOMS.
  
 10. ALL FIRE SPRINKLER SYSTEMS SHALL COMPLY WITH NFPA
 13.
  
 11. ALL FIRE ALARM SYSTEMS SHALL COMPLY WITH NFPA 72.
  
 12. DEMOLITION, RENOVATION AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 13. PLEASE PROVIDE FLAME SPREAD DETAILS ON FOAM EIFS
 BANDS PLANNED FOR THE BUILDINGS.
  
 14. EXITS ARE TO BE PROVIDED DURING CONSTRUCTION.
  
 15. FIRE AND PARAMEDICAL ACCESS IS TO BE PROVIDED
 DURING CONSTRUCTION.
  
 16. LIFE SAFETY PLANS ARE TO BE PROVIDED FOR EACH
 BUILDING ILLUSTRATING EXITS, TRAVEL DISTANCES, DEAD-END
 CORRIDORS, OCCUPANT LOADS, ETC.
  
 17. PLEASE PROVIDE MORE DETAILS ON EMERGENCY PHONES.
  
 18. ALL ELECTRICAL APPLIANCES, FIXTURES, AND DEVICES
 SHALL COMPLY WITH NFPA 70, THE NATIONAL ELECTRICAL
 CODE.
  
 19. PLEASE ILLUSTRATE ALL PORTABLE FIRE EXTINGUISHER
 LOCATIONS.
  
 20. SEVERAL OF THE RETAIL STORES WILL BE CLASSIFIED AS
 CLASS A MERCANTILE OCCUPANCIES SO THEY MUST COMPLY WITH
 THAT CATEGORY OF NFPA 101, THE LIFE SAFETY CODE, 2009
 EDITION.
  
 21. PLEASE INDICATE ON THE DRAWINGS ALL INTERIOR
 CLASSIFICATIONS FOR ALL WALLS AND CEILINGS.
  
 22. TRASH AND DEBRIS IS NOT PERMITTED TO ACCUMULATE ON
 THE CONSTRUCTION SITE.
  
 23. ALL FIRE DOORS ARE TO BE PROPERLY RATED AND TAGGED
 AND BE EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSES
 THE DOORS TO POSITIVELY LATCH. RATED FIRE DOORS ARE
 REQUIRED TO BE EQUIPPED WITH RATED HARDWARE.
  
 24. ALL FIRE RATED PENETRATIONS ARE TO BE PROPERLY
 SEALED.
  
 25. PANIC HARDWARE IS REQUIRED ON ALL DOORS SUBJECT TO
 OCCUPANT LOADS OF 100 OR MORE PERSONS. FIRE EXIT PANIC
 HARDWARE IS REQUIRED ON ALL FIRE DOORS WITH OCCUPANTS
 LOAD OF 100 ORE MORE PERSONS.
  
 26. SEATING DIAGRAMS FOR ALL RESTAURANTS IS REQUIRED.
 ALL SEATING DIAGRAMS SHALL INDICATE HANDICAPPED
 SEATING.
  
 27. LOW VOLTAGE PERMITS ARE REQUIRED FOR ALL LOW
 VOLTAGE EQUIPMENT.
  
 28. KNOX-BOXES ARE REQUIRED ON BUILDINGS FOR FIRE
 RESCUE ACCESS.
  
 29. OCCUPANT LOADS ARE TO BE DETERMINED BY THE BUREAU
 OF FIRE PREVENTION FOR ALL RESTAURANTS. THESE OCCUPANT
 LOADS ARE TO BE POSTED.
  
 30. ALL WALK-IN COOLERS AND FREEZERS SHALL BE FIRE
 SPRINKLER PROTECTED.
  
 31. ALL OUTDOOR SEATING AREAS THAT ARE COVERED ARE TO
 BE FIRE SPRINKLER PROTECTED.
  
 32. SUFFICIENT DETAILS ARE TO BE PROVIDED FOR ALL
 MEZZANINES AT THE SITE.
  
 33. SEPARATE SHOP DRAWINGS ARE REQUIRED FOR ALL FIRE
 SPRINKLER AND FIRE ALARM SYSTEM INSTALLATIONS.
  
 34. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 35. HANDRAILS ARE TO BE PROVIDED ON BOTH SIDES OF NEW
 STAIRS.
  
 36. NO WORK IS TO COMMENCE WITHOUT VALID APPROVALS AND
 PERMITS.
  
  
 DENIED
  
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE
  