| Plan Review Notes For Project Z13040037 |
| Project Number |
Z13040037 |
|
| Review Stop |
STORM |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-10-01 00:53:43 | 1. WATER METER MAY NEED TO BE LOCATED OUTSIDE FENCE | | | AREA FOR ACCESS BY CITY STAFF. | | | 2. CONSIDER UTILIZING CONCRETE WALK AS HANDICAP AISLES | | | TO REDUCE THE AMOUNT OF NEW PAVEMENT. | | | 3. SIDE SLOPES OF WEST DRY RETENTION AREA APPEAR TO BE | | | 3:1. CONSIDER CHANGING TO 4:1 OR FLATTER (HOLDING TOE | | | OF SLOPE). | | | 4. ANY REASON WHY RETENTION AREAS CANNOT BE ENLARGED TO | | | PROVIDE STORAGE/TREATMENT OF RUNOFF FROM EXISTING | | | PARKING LOT. | | | 5. SPOT GRADE ON RAMP SLOPE NORTH OF H.C. PARKING SPACE | | | APPEARS TO BE MISLABELED. SHOULD IT BE 11.90 INSTEAD OF | | | 10.90? IS A RAMP NEEDED HERE? | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING AND PUBLIC WORKS DEPARTMENT | | | 561-494-1120 |
| |