Plan Review Notes
Plan Review Notes For Project Z13040037
Project Number Z13040037
Review Stop STORM
Sequence Number 2
Notes
Date Text
2013-10-01 00:53:431. WATER METER MAY NEED TO BE LOCATED OUTSIDE FENCE
 AREA FOR ACCESS BY CITY STAFF.
 2. CONSIDER UTILIZING CONCRETE WALK AS HANDICAP AISLES
 TO REDUCE THE AMOUNT OF NEW PAVEMENT.
 3. SIDE SLOPES OF WEST DRY RETENTION AREA APPEAR TO BE
 3:1. CONSIDER CHANGING TO 4:1 OR FLATTER (HOLDING TOE
 OF SLOPE).
 4. ANY REASON WHY RETENTION AREAS CANNOT BE ENLARGED TO
 PROVIDE STORAGE/TREATMENT OF RUNOFF FROM EXISTING
 PARKING LOT.
 5. SPOT GRADE ON RAMP SLOPE NORTH OF H.C. PARKING SPACE
 APPEARS TO BE MISLABELED. SHOULD IT BE 11.90 INSTEAD OF
 10.90? IS A RAMP NEEDED HERE?
  