Plan Review Notes
Plan Review Notes For Project Z13040029
Project Number Z13040029
Review Stop PARK
Sequence Number 2
Notes
Date Text
2014-02-25 09:54:26PURSUANT TO AN EMAIL FROM SEAN SAMUELS, DATED 1/10/14,
 THE FOLLOWING COMMENTS WERE MADE:
  
 1) LOADING ZONE NEED TO PROVIDE SPECIFICATION PER CITY
 OF WPB ZLDR
 2) PROVIDE A ADA VAN ACCESSIBLE SIGN
 3) ARE STACKER PARKING LIFT OPERATED. WHAT THE HEIGHT
 4) PLEASE DOUBLE CHECK COUNT VS ACTUAL SPACES
 5) NO ADA SPACE WAS ON THE FIRST SPACE.
 6) CONCERN OF MIXING ANGLE PARKING WITH 90 DEGREE
 PARKING.
  
 SEAN SAMUELS CCP
 PARKING FACILITY SUPERVISOR
 CITY OF WEST PALM BEACH
 500 BANYAN BLVD
 WEST PALM BEACH, FL 33401
 PHONE: 561/822-1507
 CELL 561/644-7385
  
 IT WAS CONFIRMED BY JOHN ROACH, PRINCIPAL PLANNER, THAT
 THE ABOVE COMMENTS HAD BEEN ADDRESSED OR OTHERWISE
 SATISFIED THROUGH CONDITIONS OF APPROVAL.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH PRINCIPAL
 PLANNER, AT (561) 822-1448.