2013-06-17 11:57:10THE FOLLOWING COMMENTS WERE RECEIVED FROM M. CARSILLO
 VIA EMAIL ON 6/11/13...
  
 1. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, AND
 AFTER CONSTRUCTION.
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
 3. NO EXTERIOR DOORS DISPLAYED ON SHEET SP-1.
 4. ALL FIRE ACCESS LANES ARE TO BE AT LEAST 20 FEET
 WIDE, AND BE CAPABLE OF SUPPORTING FIRE AND PARAMEDICAL
 EQUIPMENT.
 5. ANY AREA THAT ANY FIRE AND PARAMEDICAL EQUIPMENT
 MUST PASS UNDER MUST PROVIDE AT LEAST 13?-6? CLEARANCE.
 6. A FIRE COMMAND ROOM MUST BE PROVIDED AND ALL
 EQUIPMENT REQUIRED SHALL BE INSTALLED IN THIS ROOM.
 7. STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
 8. TRASH AND DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
 9. PROVIDE SEPARATE PLANS AND PERMITS FOR ALL SECURITY
 AND ACCESS GATES.
 10. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOORS.
 11. STAIRWELL IDENTIFICATION SIGNS ARE REQUIRED INSIDE
 THE STAIRWELLS.
 12. ALL NEW STAIRS AND RAMPS ARE REQUIRED TO HAVE
 HANDRAILS ON BOTH SIDES.
 13. SMOKE ALARMS ARE REQUIRED WITHIN THE APARTMENTS.
 14. THE ENTIRE BUILDING IS TO BE EQUIPPED WITH A
 COMPLETE AUTOMATIC FIRE SPRINKLER SYSTEM.
 15. THE ENTIRE BUILDING IS TO BE EQUIPPED WITH A
 COMPLETE FIRE ALARM SYSTEM WITH VOICE EVACUATION.
 16. PLEASE DECLARE CONSTRUCTION TYPE FOR THE BUILDING.
 17. PLEASE PROVIDE A LIFE SAFETY PLAN ILLUSTRATING
 OCCUPANT LOADS, TRAVEL DISTANCES, DEAD-END CORRIDORS,
 AND ALL FIRE SAFETY EQUIPMENT.
 18. PLEASE ILLUSTRATE ALL VERTICAL AND HORIZONTAL FIRE
 SEPARATIONS.
 19. PLEASE ILLUSTRATE ALL FIRE RATINGS OF ALL VERTICAL
 SHAFTS.
 20. PLEASE PROVIDE A DOOR SCHEDULE INDICATING FIRE
 RATINGS AND APPROPRIATE HARDWARE.
 21. PLEASE PROVIDE DETAILS ON ALL STAIRS. (RISE, RUN,
 AND TREAD DEPTH)
 22. THE PARKING GARAGE IS TO COMPLY WITH NFPA 88A.
 23. BUILDING ADDRESS IS REQUIRED.
 24. A COMPLETE WET STANDPIPE SYSTEM IS REQUIRED FOR THE
 BUILDING.
 25. PLEASE ILLUSTRATE FIRE EXTINGUISHER LOCATIONS.
 26. BUILDING ADDRESS IS REQUIRED. A MINIMUM OF AT LEAST
 6? HIGH NUMBERS ARE REQUIRED.
 27. PLEASE EXPLAIN FIREMAN?S VESTIBULES SHOWN ON THE
 DRAWINGS.
 28. PLEASE INDICATE STRETCHER ACCESSIBLE ELEVATOR.
 29. PLEASE PROVIDE COMPLETE DETAILS ON EMERGENCY
 GENERATOR AND FIRE PUMP ASSEMBLY.
 30. PLEASE DISPLAY ALL EMERGENCY LIGHTS AND ILLUMINATED
 EXIT SIGNS FOR THE PROJECT.
 31. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR GLASS RAILING.
 32. SEPARATE PLANS AND PERMITS REQUIRED FOR APARTMENT
 CONSTRUCTION.
 33. PLEASE DESCRIBE WHAT ACTIVITIES WILL OCCUR ON THE
 MEZZANINE AND AMENITY LEVEL.
 34. A KNOX-BOX WILL BE REQUIRED FOR THE PROJECT.
 35. PLEASE PROVIDE PRESSURIZATION INFORMATION FOR THE
 STAIRS AND ELEVATOR SHAFTS.
 36. PLEASE PROVIDE DETAILS ON FUEL USE, STORAGE, AND
 HANDLING FOR THE GENERATOR.
 37. PLEASE DESCRIBE FIRE SEPARATION FOR THE MECHANICAL,
 MAINTENANCE, AND LOADING DOCK AREA.
 38. ELEVATOR WARNING SIGNS WILL BE REQUIRED AT ALL
 ELEVATOR OPENINGS.
 39. ANY CANOPY THAT IS CONSTRUCTED OF COMBUSTIBLE
 MATERIALS OR IS ABOVE ANY STORAGE SHALL BE FIRE
 SPRINKLER PROTECTED.
 40. THE PROPOSED 8? FIRE MAIN APPEARS TO BE A DEAD-END
 MAIN. THIS MAIN SHOULD BE COMPLETELY LOOPED.
 41. KNOX-BOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS. (FDC)
 42. PLEASE PROVIDE DETAILS ON ALL INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
 43. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
 44. PLEASE PROVIDE DETAILS ON GARAGE EXHAUST SYSTEM.
 45. MORE INFORMATION NEEDED ON THE CONSTRUCTION OF THE
 COOLING TOWER DISPLAYED ON PAGE A-8.
 46. PLEASE PROVIDE STAIR ELEVATIONS.
 47. PLEASE INDICATE HOW FIRE RESCUE COMMUNICATIONS WILL
 BE ACHIEVED IN THIS HIGH-RISE RESIDENTIAL BUILDING. IS
 A BIDIRECTIONAL AMPLIFICATION DEVICE PLANNED TO BE
 USED.
 48. THE VEHICLES DISPLAYED ON AUTO-TURN EXHIBIT ARE NOT
 REPRESENTATIVE OF THE LARGEST VEHICLES FIRE RESCUE WILL
 USED TO RESPOND TO THIS LOCATION.
 49. PLEASE PROVIDE OCCUPANT LOADS FOR ALL FLOORS AND
 ALL LOCATIONS.
 50. PLEASE DISPLAY LOCATIONS WHERE ?NO EXIT? SIGNS WILL
 NEED TO BE PLACED TO AVOID CONFUSION.
 51. ALL ELECTRICAL EQUIPMENT AND DEVICES TO COMPLY WITH
 NFPA 70, THE NATIONAL ELECTRICAL CODE.
 52. ALL LIGHTNING PROTECTION TO COMPLY WITH NFPA 780.
 53. PROPER CLEARANCES ARE TO BE PROVIDED TO FIRE
 HYDRANTS.
  
 DENIED
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE
  