Plan Review Notes
Plan Review Notes For Project Z13040029
Project Number Z13040029
Review Stop STORM
Sequence Number 1
Notes
Date Text
2013-05-08 11:44:301. PROVIDE COPY OF SFWMD ERP OR NO-NOTICE PERMIT PRIOR
 TO START OF CONSTRUCTION.
 2. PROVIDE COPY OF NPDES NOI PERMIT PRIOR TO START OF
 CONSTRUCTION.
 3. PROVIDE DRAINAGE CALCULATIONS, INCLUDING LAND USE
 BREAKDOWN (PERVIOUS, IMPERVIOUS, BUILDING, ETC), WATER
 QUALITY TREATMENT, ETC., WITH THE CITY'S ENGINEERING
 PERMIT APPLICATION.
 4. PROVIDE SWPPP PLAN WITH THE CITY'S ENGINEERING
 PERMIT APPLICATION.
 5. INDICATE VERTICAL DATUM ON THE PLANS (SHOULD BE NGVD
 1929).
 6. RE-ROUTING OF OUTFALL PIPING OF FLAGLER DRIVE
 DRAINAGE TO BE DESIGNED TO HAVE NO ADVERSE IMPACT TO
 THE HYDRAULIC GRADE LINE OF THE FLAGLER DRIVE DRAINAGE
 SYSTEM.
 7. PROVIDE AN EASEMENT IN FAVOR OF THE CITY OVER THE
 RE-DIRECTED DRAINAGE SYSTEM CONVEYING RUNOFF FROM
 FLAGLER DRIVE TO THE OUTFALL.
 8. SUGGEST PLUG AND GROUT FILL THE OUTFALL PIPE
 PROPOSED TO BE ABANDONED AT SEAWALL.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT