Review Stop STORM
Sequence Number 5
Notes
Date Text
2014-09-10 12:46:471. PROPOSED PERIMETER GRADES SHOULD BE NO LOWER THAN
 THE PEAK STAGE OF20.56' NGVD FOR THE 25-YEAR 3-DAY
 DESIGN STORM. THERE IS A SPOT ELEVATION OF 20.25
 LOCATED SE OF STRUCTURE D-9.
  
 2. THE NORTH AND EAST PIPE CONNECTIONS TO STRUCTURE D-9
 WILL NOT FIT INTO THE STRUCTURE, GIVEN THE PIPE INVERT
 ELEVATIONS, PIPE SIZES AND GRATE ELEVATION.
  
 3. INCLUDE WEIR CONTROL STRUCTURES IN INLETS WHERE THE
 EXFILTRATION TRENCHES ARE NOT AT THE SAME ELEVATION ON
 EACH SIDE OF THE INLET. THE WEIR SHOULD BE LOCATED ON
 THE EXFILTRATION PIPE WITH THE HIGHER INVERT ELEVATION.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT