Plan Review Notes
Plan Review Notes For Project Z13040022
Project Number Z13040022
Review Stop STORM
Sequence Number 5
Notes
Date Text
2014-09-10 12:17:581.SANITARY PIPE BETWEEN S-2 AND EXISTING SANITARY
 MANHOLE IS SHOWN TO BE 43 FEET AT 0.4% SLOPE ON SHEET
 C-2. THE DESIGN PIPE INVERT ELEVATIONS ARE SHOWN TO BE
 13.73 FEET AT S-2 AND 13.66 AT EXISTING MANHOLE. THE
 PIPE SLOPE CALCULATES TO BE 0.16% USING THESE INVERT
 ELEVATIONS AND 43' PIPE LENGTH.
  
 2. TREES ARE PROPOSED OVER THE PROPOSED EXFILTRATION
 TRENCH AT SE CORNER OF SITE. RELOCATE THE TREES OR
 EXFILTRATION TRENCH.
  
 3. INCLUDE WEIRS IN THE DRAINAGE SYSTEM PRIOR TO THE
 OUTLET STRUCTURES IN THE RETENTION AREAS TO SURCHARGE
 THE EXFILTRATION TRENCHES.
  
 4. PER THE DRAINAGE EASEMENT RECORDED IN ORB 13931 PG
 621, PROVIDE AN ACCEPTANCE LETTER FROM TENET ST. MARY'S
 THAT THE PROPOSED STORMWATER MANAGEMENT SYSTEM WILL NOT
 ADVERSELY AFFECT TENET ST. MARY'S. THIS LETTER MAY BE
 SUBMITTED WITH THE ENGINEERING PERMIT APPLICATION.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120
  