2014-06-03 11:18:231. RESPONSE TO ROUND 3 OF COMMENTS INDICATED DRAINAGE
 CALCULATIONS WERE ATTACHED. THESE CALCULATIONS WERE NOT
 FOUND IN THE 6/3/14 SUBMITTAL PACKAGE.
 2. VERIFY SLOPE/PIPE INVERTS OF SANITARY PIPE BETWEEN
 STRUCTURE S-2 AND EXISTING SANITARY MANHOLE.
 3. PER THE DRAINAGE EASEMENT RECORDED IN ORB 13931 PG
 621, PROVIDE AN ACCEPTANCE LETTER FROM TENET ST. MARY'S
 THAT THE PROPOSED STORMWATER MANAGEMENT SYSTEM WILL NOT
 ADVERSELY AFFECT TENET ST. MARY'S. THIS LETTER MAY BE
 SUBMITTED WITH THE ENGINEERING PERMIT APPLICATION.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120
  