Plan Review Notes
Plan Review Notes For Project Z13040022
Project Number Z13040022
Review Stop STORM
Sequence Number 1
Notes
Date Text
2013-05-08 11:53:231. PROVIDE COPY OF SFWMD ERP OR NO-NOTICE PERMIT PRIOR
 TO START OF CONSTRUCTION.
 2. PROVIDE COPY OF NPDES NOI PERMIT PRIOR TO START OF
 CONSTRUCTION.
 3. PROVIDE DRAINAGE CALCULATIONS, INCLUDING LAND USE
 BREAKDOWN (PERVIOUS, IMPERVIOUS, BUILDING, ETC), WATER
 QUALITY TREATMENT, ETC., WITH THE CITY'S ENGINEERING
 PERMIT APPLICATION.
 4. PROVIDE SWPPP PLAN WITH THE CITY'S ENGINEERING
 PERMIT APPLICATION.
 5. NO ENGINEERING PLANS OR CALCULATIONS PROVIDED.
 6. RELOCATE PROPOSED RETENTION AREA OUT OF THE UTILITIY
 EASEMENT.
 7. RELOCATE PROPOSED TREE FROM UTILITY EASEMENT.
 8. ELEVATIONS TO BE IN REFERENCE TO NGVD 1929.
 9. PROPOSED GRAVITY SEWER MAY "FIT" INSIDE THE 25'
 UTILITY EASEMENT. THE UE MAY CONTAIN A PUBLIC WATER
 MAIN, PRIVATE FORCE MAIN AND OVERHEAD ELECTRIC.
 10. WILL SITE HAVE MASTER WATER METER OR WILL EASEMENTS
 BE PROVIDED OVER THE WATER MAIN?
 11. SHOW EXISTING AND PROPOSED UTILITIES ON THE
 LANDSCAPE PLANS.
 12. FPL EASEMENT DIMENSION NOT SHOWN IN RIGHT PLACE ON
 LANDSCAPE PLANS.
 13. RETENTION AREA SHOULD BE LABELED PHASE 1 ON
 LANDSCAPE PLANS.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 (561) 494-1120
  