Plan Review Notes
Plan Review Notes For Project Z13040019
Project Number Z13040019
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-09-18 12:31:51NORTH OLIVIE PLACE
  
 THE NOTES PREVIOUSLY SUBMITTED BY CHIEF CARSILLO DO NOT
 APPEAR TO HAVE BEEN ADDRESSED ON THIS SUBMITTAL.
 THEREFORE, THEY WILL BE RE-SUBMITTED.
  
 06/25/2013 NORTH OLIVE PLACE
 2ND SUBMITTAL FOR THE PLANS AND PLATS REVIEW COMMITTEE
 Z13040019
 FIRE RESCUE COMMENTS
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. EXITS ARE TO BE KEPT UP WITH CONSTRUCTION
 ACTIVITIES.
  
 3. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN AS NECESSARY.
  
 4. ALL APARTMENT BUILDINGS MUST COMPLY WITH THE FLORIDA
 FIRE PREVENTION CODE, 2010 EDITION, THE LIFE SAFETY
 CODE, 2009 EDITION, MORE SPECIFICALLY CHAPTER 30, NEW
 APARTMENTS.
  
 5. ALL PARKING STRUCTURES MUST COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 CHAPTER 42 STORAGE OCCUPANCIES (PARKING STRUCTURES)
  
 6. SMOKE ALARMS ARE REQUIRED IN EVERY SLEEPING ROOM AND
 OUTSIDE OF THE SLEEPING ROOMS AND IN ALL LEVELS OF THE
 DWELLING UNITS PER NFPA 30, NEW APARTMENTS. THESE
 DETECTORS ARE TO BE HARD WIRED AND BE INTERCONNECTED TO
 ONE ANOTHER.
  
 7. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 ALL WALLS AND CEILINGS.
  
 8. FIRE SPRINKLER AND FIRE ALARM SYSTEMS WILL BE
 REQUIRED. SEPARATE PLANS AND PERMITS WILL BE REQUIRED
 PRIOR TO INSTALLATIONS.
  
 9. PLEASE INDICATE ALL VERTICAL AND HORIZONTAL FIRE
 SEPARATIONS FOR THE PROJECT.
  
 10. PLEASE ILLUSTRATE ALL FIRE RATED OPENING
 PROTECTIVES (FIRE DOORS AND HARDWARE) IN THE DOOR
 SCHEDULE.
  
 11. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS FOR THE PROJECT.
  
 12. PLEASE ILLUSTRATE ALL EXIT DISCHARGE LOCATIONS.
  
 13. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT SHALL BE ILLUSTRATED.
  
 14. BUILDING ADDRESSES ARE REQUIRED ON EACH BUILDING.
 THESE ADDRESSES ARE TO BE MINIMUM OF AT LEAST 6" HIGH
 AND CONTRAST TO THE BACKGROUND THAT THEY ARE AFFIXED
 TO.
  
 15. PLEASE PROVIDE FLAMESPREAD DETAILS ON FOAM BACKED
 STUCCO TRIM PLANNED FOR BUILDING ELEVATIONS.
  
 16. PLEASE DISPLAY ALL PORTABLE FIRE EXTINGUISHERS
 LOCATIONS.
  
 17. WET STANDPIPE SYSTEMS WILL BE REQUIRED WHEN MORE
 THAN THREE LEVELS AND MORE THAN 30 FEET EXISTS ABOVE
 GRADE. SYSTEMS ARE TO COMPLY WITH NFPA 14.
  
 18. PLEASE ENSURE PROPER FIRE SEPARATIONS EXIST BETWEEN
 PARKING STRUCTURES AND OTHER BUILDINGS.
  
 19. INFORMATION REQUIRED ON ALL STAIRS. PLEASE PROVIDE
 MINIMUM RISE, RUN, AND TREAD DEPTH FOR ALL STAIRS.
  
 20. IF PHASED CONSTRUCTION IS BEING PLANNED, COMPLETE
 DRAWINGS ARE REQUIRED PRIOR TO COMMENCING EACH PHASE OF
 THE PROJECT SO THAT THEY MAY BE REVIEWED PRIOR TO
 CONSTRUCTING.
  
 21. MORE DETAILS REQUIRED ON PEDESTRIAN BRIDGES.
  
 22. KNOX-BOXES WILL BE REQUIRED FOR THE PROJECT.
  
 23. PLEASE DECLARE CONSTRUCTION TYPES FOR ALL BUILDINGS
 PLANNED FOR THE SITE.
  
 24. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOORS.
  
 25. NO DOORS SHOWN ON EXIT STAIRS FOR PARKING GARAGE
 (GARAGE II) AND IT APPEARS THAT THE BOTH EXIT STAIRS
 TERMINATE WITHIN THE BUILDING.
  
 26. DOOR SWINGS APPEAR TO BE IMPROPER FOR PARKING
 GARAGE (GARAGE I) AND IT APPEARS THAT BOTH EXIT STAIRS
 TERMINATE WITHIN THE BUILDING.
  
 27. PLEASE PROVIDE COMPLETE LIFE SAFETY PLANS FOR EACH
 BUILDING. THESE PLANS SHOULD ILLUSTRATE OCCUPANT LOADS,
 TRAVEL DISTANCES, DEAD-END CORRIDORS AND ALL FIRE
 SAFETY EQUIPMENT.
  
 28. OCCUPANT LOADS FOR ASSEMBLY SPACES SHALL BE
 DETERMINED BY THE BUREAU OF FIRE PREVENTION. THESE
 LOADS ARE REQUIRED TO BE POSTED.
  
 29. PORTIONS OF PHASE II APPEARS TO EXTEND BEYOND THE
 PROPERTY LINES AT THE ROOF LEVEL.
  
 30. PLEASE DECLARE ON THE PLANS THE FIRE RATINGS OF ALL
 SHAFTS.
  
 31. PROPER FIRE SEPARATIONS ARE REQUIRED BETWEEN
 TENANTS.
  
 32. ELEVATOR WARNING SIGNS ARE REQUIRED AT EACH
 ELEVATOR OPENING.
  
 33. PLEASE ILLUSTRATE ALL EXISTING AND NEW FIRE
 HYDRANTS PLANNED FOR THIS DEVELOPMENT.
  
 34. PLEASE ILLUSTRATE ALL FIRE DEPARTMENT SPRINKLER
 SYSTEM CONNECTIONS FOR THE PROJECT. CIVIL DRAWINGS ONLY
 CALL OUT TWO.
  
 35. PLEASE ILLUSTRATE ALL FIRE WATER MAINS, SIZES AND
 THEIR VALVE ASSEMBLIES.
  
 36. LISTED QUICK RESPONSE FIRE SPRINKLER HEADS ARE TO
 BE INSTALLED IN THE DWELLING UNITS.
  
 37. ANNUALLY, EMERGENCY INSTRUCTIONS ARE TO BE PROVIDED
 TO EACH DWELLING UNIT. THESE INSTRUCTIONS ARE TO
 INDICATE THE LOCATION OF ALARMS, EGRESS PATHS, AND
 ACTIONS TO BE TAKEN IN THE EVENT OF A FIRE OR TO AN
 ALARM ACTIVATION.
  
 38. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE
 AT LEAST 20 MINUTE FIRE RATED AND BE EQUIPPED WITH
 SELF-CLOSING DEVICES THAT CAUSE THE DOOR TO POSITIVELY
 LATCH WHEN CLOSED.
  
 39. IF ANY ASBESTOS IS DISCOVERED IN BUILDINGS THAT ARE
 PLANNED TO BE DEMOLISHED, AN ASBESTOS REMEDIATION PLAN
 IS TO BE SUBMITTED TO THE BUILDING OFFICIAL AND FIRE
 MARSHAL.
  
 40. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE BUILDING
 REACHES THREE LEVEL OR THIRTY FEET WHILE BEING
 CONSTRUCTED.
  
  
 DENIED
  
  
  
 PETER LEDUC, BATTALION CHIEF, FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
2013-06-25 15:45:08NORTH OLIVE PLACE
 2ND SUBMITTAL FOR THE PLANS AND PLATS REVIEW COMMITTEE
 Z13040019
 FIRE RESCUE COMMENTS
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. EXITS ARE TO BE KEPT UP WITH CONSTRUCTION
 ACTIVITIES.
  
 3. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN AS NECESSARY.
  
 4. ALL APARTMENT BUILDINGS MUST COMPLY WITH THE FLORIDA
 FIRE PREVENTION CODE, 2010 EDITION, THE LIFE SAFETY
 CODE, 2009 EDITION, MORE SPECIFICALLY CHAPTER 30, NEW
 APARTMENTS.
  
 5. ALL PARKING STRUCTURES MUST COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 CHAPTER 42 STORAGE OCCUPANCIES (PARKING STRUCTURES)
  
 6. SMOKE ALARMS ARE REQUIRED IN EVERY SLEEPING ROOM AND
 OUTSIDE OF THE SLEEPING ROOMS AND IN ALL LEVELS OF THE
 DWELLING UNITS PER NFPA 30, NEW APARTMENTS. THESE
 DETECTORS ARE TO BE HARD WIRED AND BE INTERCONNECTED TO
 ONE ANOTHER.
  
 7. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 ALL WALLS AND CEILINGS.
  
 8. FIRE SPRINKLER AND FIRE ALARM SYSTEMS WILL BE
 REQUIRED. SEPARATE PLANS AND PERMITS WILL BE REQUIRED
 PRIOR TO INSTALLATIONS.
  
 9. PLEASE INDICATE ALL VERTICAL AND HORIZONTAL FIRE
 SEPARATIONS FOR THE PROJECT.
  
 10. PLEASE ILLUSTRATE ALL FIRE RATED OPENING
 PROTECTIVES (FIRE DOORS AND HARDWARE) IN THE DOOR
 SCHEDULE.
  
 11. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS FOR THE PROJECT.
  
 12. PLEASE ILLUSTRATE ALL EXIT DISCHARGE LOCATIONS.
  
 13. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT SHALL BE ILLUSTRATED.
  
 14. BUILDING ADDRESSES ARE REQUIRED ON EACH BUILDING.
 THESE ADDRESSES ARE TO BE MINIMUM OF AT LEAST 6" HIGH
 AND CONTRAST TO THE BACKGROUND THAT THEY ARE AFFIXED
 TO.
  
 15. PLEASE PROVIDE FLAMESPREAD DETAILS ON FOAM BACKED
 STUCCO TRIM PLANNED FOR BUILDING ELEVATIONS.
  
 16. PLEASE DISPLAY ALL PORTABLE FIRE EXTINGUISHERS
 LOCATIONS.
  
 17. WET STANDPIPE SYSTEMS WILL BE REQUIRED WHEN MORE
 THAN THREE LEVELS AND MORE THAN 30 FEET EXISTS ABOVE
 GRADE. SYSTEMS ARE TO COMPLY WITH NFPA 14.
  
 18. PLEASE ENSURE PROPER FIRE SEPARATIONS EXIST BETWEEN
 PARKING STRUCTURES AND OTHER BUILDINGS.
  
 19. INFORMATION REQUIRED ON ALL STAIRS. PLEASE PROVIDE
 MINIMUM RISE, RUN, AND TREAD DEPTH FOR ALL STAIRS.
  
 20. IF PHASED CONSTRUCTION IS BEING PLANNED, COMPLETE
 DRAWINGS ARE REQUIRED PRIOR TO COMMENCING EACH PHASE OF
 THE PROJECT SO THAT THEY MAY BE REVIEWED PRIOR TO
 CONSTRUCTING.
  
 21. MORE DETAILS REQUIRED ON PEDESTRIAN BRIDGES.
  
 22. KNOX-BOXES WILL BE REQUIRED FOR THE PROJECT.
  
 23. PLEASE DECLARE CONSTRUCTION TYPES FOR ALL BUILDINGS
 PLANNED FOR THE SITE.
  
 24. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOORS.
  
 25. NO DOORS SHOWN ON EXIT STAIRS FOR PARKING GARAGE
 (GARAGE II) AND IT APPEARS THAT THE BOTH EXIT STAIRS
 TERMINATE WITHIN THE BUILDING.
  
 26. DOOR SWINGS APPEAR TO BE IMPROPER FOR PARKING
 GARAGE (GARAGE I) AND IT APPEARS THAT BOTH EXIT STAIRS
 TERMINATE WITHIN THE BUILDING.
  
 27. PLEASE PROVIDE COMPLETE LIFE SAFETY PLANS FOR EACH
 BUILDING. THESE PLANS SHOULD ILLUSTRATE OCCUPANT LOADS,
 TRAVEL DISTANCES, DEAD-END CORRIDORS AND ALL FIRE
 SAFETY EQUIPMENT.
  
 28. OCCUPANT LOADS FOR ASSEMBLY SPACES SHALL BE
 DETERMINED BY THE BUREAU OF FIRE PREVENTION. THESE
 LOADS ARE REQUIRED TO BE POSTED.
  
 29. PORTIONS OF PHASE II APPEARS TO EXTEND BEYOND THE
 PROPERTY LINES AT THE ROOF LEVEL.
  
 30. PLEASE DECLARE ON THE PLANS THE FIRE RATINGS OF ALL
 SHAFTS.
  
 31. PROPER FIRE SEPARATIONS ARE REQUIRED BETWEEN
 TENANTS.
  
 32. ELEVATOR WARNING SIGNS ARE REQUIRED AT EACH
 ELEVATOR OPENING.
  
 33. PLEASE ILLUSTRATE ALL EXISTING AND NEW FIRE
 HYDRANTS PLANNED FOR THIS DEVELOPMENT.
  
 34. PLEASE ILLUSTRATE ALL FIRE DEPARTMENT SPRINKLER
 SYSTEM CONNECTIONS FOR THE PROJECT. CIVIL DRAWINGS ONLY
 CALL OUT TWO.
  
 35. PLEASE ILLUSTRATE ALL FIRE WATER MAINS, SIZES AND
 THEIR VALVE ASSEMBLIES.
  
 36. LISTED QUICK RESPONSE FIRE SPRINKLER HEADS ARE TO
 BE INSTALLED IN THE DWELLING UNITS.
  
 37. ANNUALLY, EMERGENCY INSTRUCTIONS ARE TO BE PROVIDED
 TO EACH DWELLING UNIT. THESE INSTRUCTIONS ARE TO
 INDICATE THE LOCATION OF ALARMS, EGRESS PATHS, AND
 ACTIONS TO BE TAKEN IN THE EVENT OF A FIRE OR TO AN
 ALARM ACTIVATION.
  
 38. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE
 AT LEAST 20 MINUTE FIRE RATED AND BE EQUIPPED WITH
 SELF-CLOSING DEVICES THAT CAUSE THE DOOR TO POSITIVELY
 LATCH WHEN CLOSED.
  
 39. IF ANY ASBESTOS IS DISCOVERED IN BUILDINGS THAT ARE
 PLANNED TO BE DEMOLISHED, AN ASBESTOS REMEDIATION PLAN
 IS TO BE SUBMITTED TO THE BUILDING OFFICIAL AND FIRE
 MARSHAL.
  
 40. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE BUILDING
 REACHES THREE LEVEL OR THIRTY FEET WHILE BEING
 CONSTRUCTED.
  
  
 DENIED
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE