| 2013-06-10 09:33:11 | PLANNING BOARD CASE NO. 1633A,1633B,1633C. |
| | (Z13030012,Z13030015,Z13030016,Z13030017) |
| | |
| | CONTRACTOR HAS COMPLIED WITH THE FOLLOWING. |
| | |
| | #1 BELLA VITA ESTATES PROJECT LIES UNDER THE UTILITY |
| | JURISDICTION OF PALM BEACH COUNTY WATER AND SEWER |
| | SERVICE. |
| | OBTAIN PALM BEACH COUNTY UTILITIES APPROVAL FOR |
| | AVAILABILITY. |
| | |
| | #2 SITE PAVING AND DRAINAGE WILL REQUIRE DEVELOPMENT |
| | PERMIT WITH THE CITY'S ENGINEERING SERVICES DEPARTMENT. |
| | |
| | #3 SUBMITTAL TO ENGINEERING WILL REQUIRE LOCATION OF |
| | ALL DUMPSTER AREAS AND PICK-UP LOCATIONS. PLAN MUST |
| | DEMONSTRATE PICK-UP VEHICLE MANEUVERING. |
| | |
| | SANITATION: |
| | 1.INTERIOR DIMENSIONS OF THE ENCLOSURE MUST BE A |
| | MINIMUM OF 12'-6" WIDE AND 12' DEEP. A CONCRETE PARKING |
| | STOP BAR 10' LONG MUST BE CENTERED (FROM GATES) AND |
| | INSTALLED 18" FROM THE BACK WALL. STEEL BARS WILL NEED |
| | TO BE DRILLED THRU THE STOP BAR AND INTO THE INTERIOR |
| | FLOOR OF THE ENCLOSURE TO STOP THE STOP BAR FROM MOVING |
| | WHEN THE DUMPSTER IS SET INSIDE. |
| | 2.DUMPSTER ENCLOSURE MUST HAVE A MINIMUM OF 12'-6" |
| | OPENING BETWEEN THE GATE POSTS. |
| | 3.IT IS STRONGLY SUGGESTED THAT YOU ADD A RECYCLING |
| | CENTER TO YOUR DUMPSTER ENCLOSURE, ESPECIALLY SINCE YOU |
| | WILL BE CHARGED FOR RECYCLING, WHETHER YOU USE IT OR |
| | NOT. A RECYCLING CENTER WILL CALL FOR A LARGER |
| | ENCLOSURE. |
| | 4.THE OPENING OF THE DUMPSTER ENCLOSURE MUST BE ANGLED |
| | SO THAT A 40' LONG TRUCK WITH THE FORKS EXTENDED CAN |
| | APPROACH THE OPENING AND PICK UP THE DUMPSTER WITHOUT |
| | MAKING A SHARP TURN OR A THREE POINT TURN. |
| | 5.THE TRUCK NEEDS TO HAVE NO LESS THAN A 26' HIGH |
| | VERTICAL CLEARANCE AREA FOR THE TRUCK TO PICK UP THE |
| | DUMPSTER. THIS IS THE CLEAR AREA OVER THE DUMPSTER AND |
| | WHERE THE TRUCK WILL BE STOPPED TO UNLOAD THE DUMPSTER. |
| | 6.THE TRUCK NEEDS TO HAVE NO LESS THAN 14' HIGH |
| | VERTICAL CLEARANCE AND 12' HORIZONTAL CLEARANCES FOR |
| | THE TRUCK TO DRIVE THROUGH. |
| | 7.NO FLOOR DRAIN TO THE SANITARY SEWER CAN BE INSTALLED |
| | IN THE DUMPSTER ENCLOSURE, UNLESS IT IS ROOFED SO NO |
| | RAIN WATER WILL GET INTO THE DRAIN. |
| | 8.THE DUMPSTER ENCLOSURE MUST BE LOCATED TO ALLOW THE |
| | DUMP TRUCK TO BACK UP NO MORE THAN 50' STRAIGHT BACK |
| | AFTER RESETTING THE DUMPSTER IN THE ENCLOSURE. |
| | |
| |