Plan Review Notes
Plan Review Notes For Project Z13020021
Project Number Z13020021
Review Stop STORM
Sequence Number 1
Notes
Date Text
2013-03-11 12:42:241. PROJECT DESCRIPTION DESCRIBED A 6' WALL SURROUNDING
 THE PROPERTY. SURVEY CALLS OUT EXISTING 8' WALL.
 2. CITY CONSIDERS GRAVEL COVERED AREAS AS IMPERVIOUS
 SURFACE. REVISE THE DRAINAGE CALCULATIONS ACCORDINGLY.
 3. LABEL DIMENSIONS OF DETENTION AREA.
 4. STORMWATER DETENTION AREA SHOULD BE SODDED.
 5. SUGGEST USING STEEPER SIDE SLOPES (UPTO 4:1) FOR
 DETENTION AREA TO BETTER DEFINE THE STORM WATER
 DETENTION AREA.
 6. LABEL VERTICAL DATUM ON CIVIL PLANS.
 7. USE LATEST CWPB DETAILS.
 8. REPLACE SIDEWALK AT NEW DRIVEWAY ENTRANCE WITH 6"
 THICK SLAB.
 9. VERIFY STORMATER OUTFALL PIPE IS FUNCTIONAL.
 10. PROVIDE SWPPP AND EROSION CONTROL PLAN WITH
 ENGINEERING PERMIT APPLICATION.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT