2013-03-13 08:59:01BUILDING REVIEW COMMENTS
 2010 FLORIDA BUILDING CODE
  
  
 SEE SEPARATION FROM BUILDING WALL TO PROPERTY LINE WEST
 ELEVATION. THE SURVEY CALLS FOR 1.2 ' AND YOUR SITE
 PLAN SHOWS 3 '. TABLE 602 REQUIRES A FIRE RESISTANCE
 RATING OF 1 HOUR.
  
 WILL THIS PROJECT BE A MANUFACTURED BUILDING OR OF HAND
 FRAMED CONSTRUCTION.
  
 A MINIMUM OF ONE ACCESSIBLE TOILET ROOM AND DRINKING
 FOUNTAIN WILL BE REQUIRED.
  
 THE BUILDING ENTRANCE DOOR SHALL NOT SWING INTO YOUR
 PARKING ACCESS ISLE.
  
  