| Plan Review Notes For Project Z13020021 |
| Project Number |
Z13020021 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-13 08:59:01 | BUILDING REVIEW COMMENTS | | | 2010 FLORIDA BUILDING CODE | | | | | | | | | SEE SEPARATION FROM BUILDING WALL TO PROPERTY LINE WEST | | | ELEVATION. THE SURVEY CALLS FOR 1.2 ' AND YOUR SITE | | | PLAN SHOWS 3 '. TABLE 602 REQUIRES A FIRE RESISTANCE | | | RATING OF 1 HOUR. | | | | | | WILL THIS PROJECT BE A MANUFACTURED BUILDING OR OF HAND | | | FRAMED CONSTRUCTION. | | | | | | A MINIMUM OF ONE ACCESSIBLE TOILET ROOM AND DRINKING | | | FOUNTAIN WILL BE REQUIRED. | | | | | | THE BUILDING ENTRANCE DOOR SHALL NOT SWING INTO YOUR | | | PARKING ACCESS ISLE. | | | | | | | | | LUIS MARTINEZ | | | 561-805-6710 |
| |
Print |
|