| Plan Review Notes For Project Z12110027 |
| Project Number |
Z12110027 |
|
| Review Stop |
STORM |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-07 14:14:38 | 1. ENGINEERING PLANS NOT PROVIDED OTHER THAN PRELMINARY | | | ENGINEERING SITE PLAN. | | | 2. SFWMD ENVIRONMENTAL RESOURCES PERMIT WILL BE NEEDED | | | BEFORE START OF CONSTRUCTION. | | | 3, EROSION CONTROL PLAN AND STORM WATER POLLUTION | | | PREVENTION PLAN WILL BE REQUIRED WITH FINAL ENGINEERING | | | PLANS. | | | 4. STORMWATER WATER QUALITY TREATMENT VOLUME TO BE | | | PROVIDED ON SITE (MINIMUM OF 1" OF RUNOFF FROM SITE OR | | | 2.5" RUNOFF TIMES PERCENT IMPERVIOUS). | | | 5. DRAINAGE CALCULATIONS WILL BE REQUIRED FOR | | | ENGINEERING PERMITS. | | | 6. ARCHITECTURAL SITE LAYOUT PLAN LACKING DIMENSIONS | | | FOR SIDEWALKS, OFFSETS BETWEEN PROPERTY LINE AND | | | PARKING. | | | 7. CHEVRON STRIPING ON PBL BLVD. SHOULD BE ROTATED 90 | | | DEGREES. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORM WATER ENGINEER | | | ENGINEERING AND PUBLIC WORKS DEPARTMENT | | | (561) 494-1120 | | | |
| |